320 Parameters
No.
Name/Value
33.42
Edge counter 2
function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 3 of
33.01) remains 1 until the counter is again incremented. The warning (if enabled) stays
active for at least 10 seconds.
1 = Saturate: After the limit is reached, the counter status (bit 3 of 33.01) remains 1 until
33.40
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.45) is given when the limit is reached
2
Count rising edges
0 = Disable: Rising edges are not counted
1 = Enable: Rising edges are counted
3
Count falling edges
0 = Disable: Falling edges are not counted
1 = Enable: Falling edges are counted
4...15
Reserved
0000b...1111b
33.43
Edge counter 2
source
False
True
RO1
Other [bit]
33.44
Edge counter 2
divider
1...4294967295
33.45
Edge counter 2
warn message
Edge counter 2
exceeded
Counted main
contactor
Counted output
relay
Counted motor
starts
Counted power ups
Counted DC
charges
Description
Configures signal edge counter 2.
is reset. The warning (if enabled) also stays active until
Edge counter 2 configuration word.
Selects the signal to be monitored by signal edge counter 2.
0.
1.
Bit 0 of
10.21 RO status
Source selection (see
Defines a divisor for signal edge counter 2. Determines how
many signal edges increment the counter by 1.
Divisor for signal edge counter 2.
Selects the optional warning message for signal edge counter
2.
A889 Edge counter
control panel by choosing Menu – Settings – Edit texts.
A884 Main
contactor.
A881 Output
relay.
A882 Motor
starts.
A883 Power
ups.
A885 DC
charge.
(page 188).
Terms and abbreviations
2. The message text can be edited on the
Def/FbEq16
0000b
33.40
is reset.
1 = 1
False
0
1
2
on page 148). -
1
-
Edge counter
2 exceeded
3
11
12
13
14