212 Parameters
No.
Name/Value
250 us
500 us
1 ms
2 ms
4 ms
7.9375 ms
14.32
AI1 filter time
0.000 ... 30.000 s
14.33
AI1 min
-22.000 ... 22.000
mA or V
14.34
RO1 source
14.34
AI1 max
-22.000 ... 22.000
mA or V
Description
250 microseconds.
500 microseconds.
1 millisecond.
2 milliseconds.
4 milliseconds.
7.9375 milliseconds.
(Visible when
14.01 Module 1 type
Defines the filter time constant for analog input AI1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Note: The signal is also filtered due to the signal interface
hardware. See parameter
Filter time constant.
(Visible when
14.01 Module 1 type
Defines the minimum value for analog input AI1.
See also parameter
14.21 AI
Minimum value of AI1.
(Visible when
14.01 Module 1 type
Selects a drive signal to be connected to relay output RO1.
For the available selections, see parameter
output
source.
(Visible when
14.01 Module 1 type
Defines the maximum value for analog input AI1.
See also parameter
14.21 AI
Maximum value of AI1.
=
FIO-11
or FAIO-01)
t
)
14.31 AI1 filter
gain.
=
FIO-11
or FAIO-01)
tune.
=
FIO-01
or FDIO-01)
14.11 DIO1
=
FIO-11
or FAIO-01)
tune.
Def/FbEq16
2
3
4
5
6
7
0.100 s
1000 = 1 s
0.000 mA or
V
1000 = 1 mA
or V
Not
energized
10.000 mA or
V
1000 = 1 mA
or V