ABB +N5600 Firmware Instructions page 476

Single drive
Table of Contents

Advertisement

476 Parameters
No.
Name/Value
95.13
Reduced run mode
0...65535
95.14
Connected modules
Bit
Name
0
Module 1
1
Module 2
...
...
11
Module 12
12...15 Reserved
0000h...FFFFh
95.15
Special HW
settings
Bit
Name
0
EX motor
1
ABB sine filter
2
High speed mode
3
Custom sine filter
4...15
Reserved
0000b...0111b
Description
(Only visible with a BCU control unit)
Specifies the number of inverter modules available.
This parameter must be set if reduced run is required. A value
other than 0 activates the reduced run function.
If the control program cannot detect the number of modules
specified by this parameter, a fault
generated.
See section
Reduced run function
0 = Reduced run disabled
1...12 = Number of modules available
Number of inverter modules available
(Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules have
been detected by the control program.
Description
1 = Module 1 has been detected.
1 = Module 2 has been detected.
...
1 = Module 12 has been detected.
Inverter modules connected.
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
Information
1 = The driven motor is an Ex motor provided by ABB for potentially
explosive atmospheres. This sets the required minimum switching
frequency for ABB Ex motors. Note: For non-ABB Ex motors,
contact your local ABB representative.
1 = An ABB sine filter is connected to the output of the drive/inverter.
1 = Minimum switching frequency limit adaptation to output
frequency active. This setting improves control performance at high
output frequencies (typically above 120 Hz).
1 = A custom sine filter is connected to the output of the
drive/inverter. See also parameters 97.01, 97.02, 99.18, 99.19.
Hardware options configuration word.
(5695 Reduced
run) is
(page 128).
Def/FbEq16
0
-
-
1 = 1
-
1 = 1