95

95 HW configuration

95.01
Supply voltage
Not given
208...240 V
380...415 V
440...480 V
500 V
525...600 V
660...690 V
Description
(Only visible when IGBT supply unit control activated by
95.20)
Defines the DC voltage reference for the supply unit when
94.21 DC voltage ref source
User DC reference.
(Only visible when IGBT supply unit control activated by
95.20)
Displays the reactive power reference sent to the supply unit.
This parameter is read-only.
Reactive power reference sent to the supply unit.
(Only visible when IGBT supply unit control activated by
95.20)
Selects the source of the reactive power reference to be sent
to the supply unit.
None.
94.32 User reactive power
Source selection (see
Terms and abbreviations
(Only visible when IGBT supply unit control activated by
95.20)
Defines the reactive power reference for the supply unit when
94.31 Reactive power ref source
User reactive power reference.
Various hardware-related settings.
Selects the supply voltage range. This parameter is used by
the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings and
the DC voltage control functions (trip and brake chopper
activation limits) of the drive.
WARNING! An incorrect setting may cause the motor
to rush uncontrollably, or the brake chopper or resistor
to overload.
Note: The selections shown depend on the hardware of the
drive. If only one voltage range is valid for the drive in
question, it is selected by default.
No voltage range selected. The drive will not start modulating
before a range is selected.
208...240 V
380...415 V
440...480 V
500 V
525...600 V
660...690 V
is set to
User
ref.
reference.
on page 148). -
is set to
User
ref.
Parameters 473
Def/FbEq16
0.0 V
10 = 1 V
-
10 = 1 kvar
User ref
0
1
0.0 kvar
10 = 1 kvar
-
0
1
2
3
4
5
6