Control Interfaces; Programmable Analog Inputs; Programmable Analog Outputs; Programmable Digital Inputs And Outputs - ABB +N5600 Firmware Instructions

Single drive
Table of Contents

Advertisement

64 Program features

Control interfaces

Programmable analog inputs

The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2...10 V or -10...10 V) or current (0/4...20 mA)
input by a jumper or switch on the control unit. Each input can be filtered, inverted
and scaled. The analog inputs on the control unit are read on a 0.5 ms time level.
The number of analog inputs can be increased by installing FIO-11 or FAIO-01 I/O
extensions (see
Programmable I/O extensions
extension modules are read on a 2 ms time level.
The drive can be set to perform an action (for example, to generate a warning or fault)
if the value of an analog input moves out of a predefined range.
Settings
Parameter group
12 Standard AI

Programmable analog outputs

The control unit has two current (0...20 mA) analog outputs. Each output can be
filtered, inverted and scaled. The analog outputs on the control unit are updated on a
0.5 ms time level.
The number of analog outputs can be increased by installing FIO-11 or FAIO-01 I/O
extensions (see
Programmable I/O extensions
extension modules are updated on a 2 ms time level.
Settings
Parameter group
13 Standard AO

Programmable digital inputs and outputs

The control unit has six digital inputs, a digital start interlock input, and two digital
input/outputs (I/O that can be set as either an input or an output). The digital inputs on
the control unit are read on a 0.5 ms time level.
One digital input (DI6) doubles as a PTC thermistor input. See section
protection
(page 116).
Digital input/output DIO1 can be used as a frequency input, DIO2 as a frequency
output.
The number of digital inputs/outputs can be increased by installing FIO-01, FIO-11 or
FDIO-01 I/O extensions (see
on extension modules are read on a 2 ms time level.
below). The analog inputs on
(page 196).
below). The analog outputs on
(page 200).
Programmable I/O extensions
Motor thermal
below). The digital inputs

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents