ABB +N5600 Firmware Instructions page 461

Single drive
Table of Contents

Advertisement

No.
Name/Value
91.02
Module 1 status
No option
No communication
Unknown
FEN-01
FEN-11
FEN-21
FEN-31
FSE-31
91.03
Module 2 status
91.04
Module 1
temperature
0...1000 °C, °F or
ohm
91.06
Module 2
temperature
0...1000 °C, °F or
ohm
91.10
Encoder parameter
refresh
Done
Refresh
91.11
Module 1 type
None
FEN-01
FEN-11
FEN-21
FEN-31
Description
Displays the type of the interface module found in the location
specified by parameter
91.12 Module 1
This parameter is read-only.
No module detected in the specified slot.
A module has been detected but cannot be communicated
with.
The module type is unknown.
An FEN-01 module has been detected and is active.
An FEN-11 module has been detected and is active.
An FEN-21 module has been detected and is active.
An FEN-31 module has been detected and is active.
An FSE-31 module has been detected and is active.
Displays the type of the interface module found in the location
specified by parameter
91.14 Module 2
For the indications, see parameter
This parameter is read-only.
Displays the temperature measured through the sensor input
of interface module 1. The unit is selected by parameter
96.16 Unit
selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
Temperature measured through interface module 1.
Displays the temperature measured through the sensor input
of interface module 2. The unit is selected by parameter
96.16 Unit
selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
Temperature measured through interface module 2.
Validates any changed encoder interface module parameters.
This is needed for any parameter changes in groups 90...93
to take effect.
After refreshing, the value reverts automatically to Done.
Notes:
• Permanent magnet motors only: The drive will perform a
fresh autophasing routine (see page 96) at next start if the
motor feedback encoder settings have been changed.
• The parameter cannot be changed while the drive is
running.
Refreshing done.
Refreshing.
Defines the type of the module used as interface module 1.
None (communication disabled).
FEN-01.
FEN-11.
FEN-21.
FEN-31.
Parameters 461
location.
location.
91.02 Module 1
status.
Def/FbEq16
-
0
1
2
16
17
18
21
25
-
-
-
-
-
Done
0
1
None
0
1
2
3
4