ABB +N5600 Firmware Instructions page 324

Single drive
Table of Contents

Advertisement

324 Parameters
No.
Name/Value
35.04
FPTC status word
Bit
Name
0
Module found in slot 1
1
Fault active in slot 1
2
Warning active in slot 1 1 = Yes: The module in slot 1 has an active warning (A497).
3
Module found in slot 2
4
Fault active in slot 2
5
Warning active in slot 2 1 = Yes: The module in slot 2 has an active warning (A498).
6
Module found in slot 3
7
Fault active in slot 3
8
Warning active in slot 3 1 = Yes: The module in slot 3 has an active warning (A499).
9...15 Reserved
0000h...FFFFh
35.11
Temperature 1
source
Disabled
Estimated
temperature
Description
Displays the status of optional FPTC-xx thermistor protection
modules. The word can be used as the source of eg. external
events.
Note: The "module found" bits are updated regardless of
whether the corresponding module is activated. However, the
"fault active" and "warning active" bits are not updated if the
module is not activated. Modules are activated by parameter
35.30 FPTC configuration
This parameter is read-only.
Description
1 = Yes: An FPTC-xx module has been detected in slot 1.
1 = Yes: The module in slot 1 has an active fault (4991).
1 = Yes: An FPTC-xx module has been detected in slot 2.
1 = Yes: The module in slot 2 has an active fault (4992).
1 = Yes: An FPTC-xx module has been detected in slot 3.
1 = Yes: The module in slot 3 has an active fault (4993).
FPTC-xx status word.
Selects the source from which measured temperature 1 is
read.
For wiring examples, see the hardware manual of the drive.
Usually this source is from a sensor connected to the motor
controlled by the drive, but it could be used to measure and
monitor a temperature from other parts of the process as long
as a suitable sensor is used as per the selection list.
None. Temperature monitoring function 1 is disabled.
Estimated motor temperature (see parameter
estimated
temperature).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient temperature
of the motor in
35.50 Motor ambient
word.
35.01 Motor
temperature.
Def/FbEq16
-
1 = 1
Disabled
0
1

Hide quick links: