ABB +N5600 Firmware Instructions page 435

Single drive
Table of Contents

Advertisement

No.
Name/Value
Linear
Quadratic
79.48
Overload delay time
0.0...30000.0 s
79.49
Overload event
reaction
Not selected
Warning
Warning with
shutdown
Fault
Recovery - Warning Overload condition triggers the overload recovery sequence.
Recovery - Fault
79.51
Overload curve
point 1
-30000.00...
30000.0 0
79.52
Overload curve
point 2
-30000.00...
30000.0 0
Description
Overload limit is calculating by formula:
T
= T
* (I
/ I
)
act
set
lim
act
Where,
T
=
79.91 Overload trip count down
act
T
=
79.48 Overload delay time
set
I
=
79.90 Overload actual limit
lim
I
=
79.42 Overload supervision signal
act
2
T
= T
* (I
/ I
)
act
set
lim
act
Where,
T
=
79.91 Overload trip count down
act
T
=
79.48 Overload delay time
set
I
=
79.90 Overload actual limit
lim
I
=
79.42 Overload supervision signal
act
Defines the time used as on-delay for the overload protection
function to react to the overload condition.
Overload delay in seconds.
Defines the response to the overload condition.
If the overload supervision signal is above active overload
limit in the defined delay time, then overload protection
function trigger the reaction defined in this parameter setting.
Overload event reaction is inactive.
Overload condition triggers the drive event
warning. It will stay on as long as overload condition is
present. The warning will automatically disappear if overload
supervision signal stays below the overload limit for the time
defined in parameter
79.48 Overload delay
Overload condition triggers the drive event
warning and immediate stop command. Drive will stop
according to parameter
Overload condition triggers the drive event
fault which immediately trips the drive.
In case recovery routine helps, the motor speed returns to
production speed. If not, drive generates the event
Overload
warning. It will stay on as long as overload condition
is present. The warning will automatically disappear if
overload supervision signal stays below the overload limit for
the time defined in parameter
Overload condition triggers the overload recovery sequence.
In case recovery routine helps, motor speed returns to
production speed. If not, drive generates the event
Overload
fault which immediately trips the drive.
Defines overload curve point 1 load limit active at
corresponding speed set in parameter
speed point
1.
Overload curve point 1.
Defines overload curve point 2 load limit active at
corresponding speed set in parameter
speed point
2.
Overload curve point 2.
D208 Overload
time.
D208 Overload
21.03 Stop mode
setting.
D101 Overload
79.48 Overload delay
79.01 Load curve
79.02 Load curve
Parameters 435
Def/FbEq16
10.0
1 = 1s
Warning
D208
time.
D101
0.00
10 = 1
0.00
10 = 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents