Check the positions of jumpers J1 and J2 on the control unit of the drive.
These jumpers determine whether analog inputs AI1 and AI2 are current or voltage.
Check/adjust the following parameters.
Select the unit to either mA or V,
corresponding to jumper J1 setting.
Configure analog inputs if used for drive
control:
Parameters
12.17
and
and high limits of the analog input signal.
Scaling parameters
12.19
the internal signal levels that correspond to
the low and high limits. See graph below.
AI (scaled)
12.20
12.17
12.19
The corresponding parameters for analog
input AI2 are 12.27...12.30.
4 – Jumpers position
12.18
– set the low
and
12.20
– define
AI (mA/V)
12.18
Quick start-up guide 35
12.15 AI1 unit selection
12.17 AI1 min
12.18 AI1 max
12.19 AI1 scaled at AI1 min
12.20 AI1 scaled at AI1 max
12.27 AI2 min
12.28 AI2 max
12.29 AI2 scaled at AI2 min
12.30 AI2 scaled at AI2 max