ABB +N5600 Firmware Instructions page 322

Single drive
Table of Contents

Advertisement

322 Parameters
No.
Name/Value
33.55
Value counter 1
warn message
Value counter 1
exceeded
Maintain motor
bearing
33.60
Value counter 2
actual
-2147483008 ...
2147483008
33.61
Value counter 2
warn limit
-2147483008 ...
2147483008
33.62
Value counter 2
function
Bit
Function
0
Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 5 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 5 of 33.01) switches to 1,
and remains so until
is reset.
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.65) is given when the limit is reached
2...15
Reserved
0000b...0011b
33.63
Value counter 2
source
Not selected
Motor speed
Description
Selects the optional warning message for value counter 1.
A88A Value counter
1. The message text can be edited on
the control panel by choosing Menu – Settings – Edit texts.
A880 Motor
bearing.
Displays the actual present value of value counter 2.
The value of the source selected by parameter
counter 2 source
is read at one-second intervals and added
to the counter. A divisor can be applied to the count (see
33.64 Value counter 2
divider).
When the counter exceeds the limit set by
counter 2 warn
limit, bit 5 of
The warning specified by
message
is also given if enabled by
function.
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
Actual present value of value counter 2.
Sets the limit for value counter 2.
With a positive limit, bit 5 of
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 5 of
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
Limit for value counter 2.
Configures value counter 2.
33.60
is reset. The warning (if enabled) also stays active until
Value counter 2 configuration word.
Selects the signal to be monitored by value counter 2.
None (counter disabled).
01.01 Motor speed used
33.63 Value
33.61 Value
33.01 Counter status
33.65 Value counter 2 warn
33.62 Value counter 2
33.01 Counter status
33.01 Counter status
(see page 152).
Def/FbEq16
Value
counter 1
exceeded
4
10
-
is set to 1.
-
0
is set to 1
is set to 1
-
0000b
33.60
1 = 1
Not selected
0
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents