ABB +N5600 Firmware Instructions page 219

Single drive
Table of Contents

Advertisement

No.
Name/Value
14.76
AO1 actual value
0.000 ... 22.000 mA Value of AO1.
14.77
AO1 source
Zero
Motor speed used
Output frequency
Motor current
Motor torque
DC voltage
Power inu out
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torq ref used
Freq ref used
Process PID out
Process PID fbk
Process PID act
Process PID dev
Force Pt100
excitation
Force KTY84
excitation
Force PTC
excitation
Force Pt1000
excitation
AO1 data storage
AO2 data storage
Other
14.78
AO1 force data
0.000 ... 22.000 mA Forced value of analog output AO1.
Description
(Visible when
14.01 Module 1 type
Displays the value of AO1 in mA.
This parameter is read-only.
(Visible when
14.01 Module 1 type
Selects a signal to be connected to analog output AO1.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 152).
01.10 Motor torque
(page 152).
01.11 DC voltage
(page 152).
01.14 Output power
(page 153).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
26.02 Torque reference used
28.02 Frequency ref ramp output
40.01 Process PID output actual
40.02 Process PID feedback actual
40.03 Process PID setpoint actual
40.04 Process PID deviation actual
The output is used to feed an excitation current to 1...3 Pt100
sensors. See section
Motor thermal protection
The output is used to feed an excitation current to a KTY84
sensor. See section
Motor thermal protection
The output is used to feed an excitation current to 1...3 PTC
sensors. See section
Motor thermal protection
The output is used to feed an excitation current to 1...3
Pt1000 sensors. See section
116).
13.91 AO1 data storage
13.92 AO2 data storage
Source selection (see
Terms and abbreviations
(Visible when
14.01 Module 1 type
Forced value that can be used instead of the selected output
signal. See parameter
14.71 AO force
=
FIO-11
or FAIO-01)
=
FIO-11
or FAIO-01)
(page 152).
(page 152).
(page 257).
(page 257).
(page 263).
(page 279).
(page 285).
(page 341).
(page 341).
(page 341).
(page 341).
(page 116).
(page 116).
(page 116).
Motor thermal protection
(page 204).
(page 204).
on page 148). -
=
FIO-11
or FAIO-01)
selection.
Parameters 219
Def/FbEq16
-
1000 = 1 mA
Zero
0
1
3
4
6
7
8
10
11
12
13
14
16
17
18
19
20
21
22
23
(page
37
38
0.000 mA
1000 = 1 mA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents