440 Parameters
No.
Name/Value
EFB1 ref
EFB2 ref
Other
80.40
IR compensation
enable
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
ESP CW bit 11
Other
80.41
IR compensation
ref
0.00...50.00 %
80.42
Step up frequency
2.00...300.00 Hz
80.80
Flux correction
-100.00...100.00 %
80.81
Flux reference
0.00...200.00 %
80.82
Actual additive
voltage
-100.00...100.00 %
81

81 Pump cleaning

81.01
Pump cleaning
enable
Description
See parameter
03.09 EFB reference 1
See parameter
03.10 EFB reference 2
Source selection (see
Terms and abbreviations
Defines the source for the IR compensation enable signal.
Validate tuning cmd is not selected.
Validate tuning cmd is selected.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
Digital input/output DIO2
Parameter
74.01 ESP control
enable/disable status of the function.
Source selection (see
Terms and abbreviations
Defines IR compensation reference value that produces
relative output voltage boost.
IR compensation reference.
Defines step-up frequency reference used for IR-
compensation.
Step up frequency.
Displays change in flux reference calculated out of additive
voltage settings in custom user U/F curve.
Flux correction.
Displays the flux reference used for the motor control when
U/F curve setting is in use.
Note: This value has no effect if energy optimization is
enabled.
Flux reference.
Displays the used additive voltage based on U/F curve setting
and actual motor speed.
Actual additive voltage.
Enables pump cleaning function.
See section
Pump impeller cleaning
Defines the source for the Cleaning function enable signal.
The function requires enable signal ON + some of the triggers
active. This creates a cleaning request. If both conditions are
achieved, then the drive is started.
The ESP control program will first perform the cleaning
routine as per settings in parameters 81.20...81.48. From the
last cleaning step, the function will automatically continue to
production operation.
Note: Cleaning function cannot be triggered when motor is
running.
(page 156).
(page 156).
on page 148). -
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(11.02 DIO delayed
status, bit 0).
(11.02 DIO delayed
status, bit 1).
word, bit-11 status controls
on page 148). -
(page 59).
Def/FbEq16
5
6
ESP CW bit
11
0
1
2
3
4
5
6
7
8
9
10
0.00
10 = 1%
2.00
10 = 1Hz
0.00
10 = 1%
0.00
10 = 1%
0.00
10 = 1%
ESP CW bit
12