Highlight Parameters and press
(Select).
Highlight Complete list using
and press
(Select).
A listing of parameter groups is displayed.
Select motor type.
Note: ESP control program supports
Asynchronous and Permanent Magnet
Synchronous motors.
Verify used Motor control mode.
Note: ESP application requires
mode selection,
DTC
mode can be used only
in cases where no step-up transformer is
needed between drive and motor.
Set motor nominal current.
Note: If step-up transformer is in use, then
nominal current setting in the drive is always
calculated for the primary side of the
transformer, i.e.
99.06 Motor nominal current
= Motor plate nominal current * Transformer
ratio.
Set motor nominal voltage.
Note: For applications with sine filter and
step-up transformer in use, the nominal
voltage setting in the drive is calculated for
the primary side of the transformer with
consideration for the resistive and inductive
losses along the circuit, i.e.
nominal voltage
= (Motor plate nominal
voltage / Transformer ratio) + circuit voltage
losses (typically ~10%).
Local
Parameters
Favorites
By function
Complete list
Modified
Back
and
Local
Complete list
01 Actual values
03 Input references
04 Warnings and faults
05 Diagnostics
06 Control and status words
07 System info
Back
99.03 Motor type
99.04 Motor control mode
SMC
control
99.06 Motor nominal current
99.07 Motor nominal voltage
99.07 Motor
Quick start-up guide 33
0.0 rpm
12:36
Select
0.0 rpm
12:36
Select