402 Parameters
No.
Name/Value
60.52
DDCS controller
node address
1...254
60.55
DDCS controller
HW connection
Ring
Star
60.56
DDCS controller
baud rate
1 mbps
2 mbps
4 mbps
8 mbps
60.57
DDCS controller
link control
1...15
Description
Selects the node address of the drive for communication with
the external controller. No two nodes on-line may have the
same address.
With an AC 800M (CI858) DriveBus connection, drives must
be addressed 1...24.
With an AC 80 DriveBus connection, drives must be
addressed 1...12.
With optical ModuleBus, the drive address is set according to
the position value as follows:
1. Multiply the hundreds of the position value by 16.
2. Add the tens and ones of the position value to the result.
For example, if the position value is 101, this parameter must
be set to 1×16 + 1 = 17.
Node address.
Selects the topology of the fiber optic link with an external
controller.
The devices are connected in a ring topology. Forwarding of
messages is enabled.
The devices are connected in a star topology (for example,
through a branching unit). Forwarding of messages is
disabled.
Selects the communication speed of the channel selected by
parameter
60.51 DDCS controller comm
1 megabit/second.
2 megabit/second.
4 megabit/second.
8 megabit/second.
Defines the light intensity of the transmission LED of RDCO
module channel CH0. (This parameter is effective only when
parameter
60.51 DDCS controller comm port
CH
0. FDCO modules have a hardware transmitter current
selector.)
In general, use higher values with longer fiber optic cables.
The maximum setting is applicable to the maximum length of
the fiber optic link. See
master/follower link
(page 74).
Light intensity.
port.
is set to
Specifications of the fiber optic
Def/FbEq16
1
Star
0
1
4 mbps
1
2
4
8
10
RDCO