AI3 unit selection
V
mA
14.61
AI3 filter gain
No filtering
125 us
250 us
500 us
1 ms
2 ms
4 ms
7.9375 ms
14.62
AI3 filter time
0.000 ... 30.000 s
Description
Milliamperes.
(Visible when
14.01 Module 1 type
Selects the unit for readings and settings related to analog
input AI3.
Note: This setting must match the corresponding hardware
setting on the I/O extension module (see the manual of the
I/O extension module). The hardware setting is shown by
parameter
14.59 AI3 HW switch
either by cycling the power or through parameter
Control board boot
is required to validate any changes in the
hardware settings.
Volts.
Milliamperes.
(Visible when
14.01 Module 1 type
Selects a hardware filtering time for AI3.
See also parameter
14.62 AI3 filter
No filtering.
125 microseconds.
250 microseconds.
500 microseconds.
1 millisecond.
2 milliseconds.
4 milliseconds.
7.9375 milliseconds.
(Visible when
14.01 Module 1 type
Defines the filter time constant for analog input AI3.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Note: The signal is also filtered due to the signal interface
hardware. See parameter
Filter time constant.
= FIO-11)
position. I/O module reboot
= FIO-11)
time.
= FIO-11)
t
)
14.61 AI3 filter
gain.
Parameters 217
Def/FbEq16
10
mA
96.08
2
10
1 ms
0
1
2
3
4
5
6
7
0.100 s
1000 = 1 s