8.1.6.13 How Should I Set and Add a NetCol5000-A025/A035/A042/A050
Parameters (Modbus-TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE_1 port on the
NetCol5000-A025/NetCol5000-A035/NetCol5000-A042/NetCol5000-A050 main control
board, and the other end has been connected to the PoE port on the ETH converter.
Context
The following describes how to set and add a NetCol5000-A042.
Procedure
Step 1 Set NetCol5000-A042 monitoring parameters.
1.
2.
3.
Step 2 Set the running parameters and control parameters for the NetCol5000-A042 on the WebUI.
1.
2.
3.
4.
Issue 06 (2020-04-22)
Click Test Connect to check whether the PDC DC meter connects to the ECC800-Pro
properly.
If the PDC DC meter connects to the ECC800-Pro properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the PDC DC meter does not connect to the ECC800-Pro properly, check whether
the cable between the PDC DC meter and the ECC800-Pro is connected properly,
whether the PDC DC meter and ECC800-Pro are running properly, and whether the
input parameters are consistent with the PDC DC meter parameters.
Enter the NetCol5000-A042 home page, click Settings, choose the user name admin,
and enter password 000001. After login, the settings screen of the NetCol5000-A042 is
displayed.
Choose Comm Settings > IP Settings, set IP assigning mode to Automatic (DHCP),
and click Submit.
Choose Settings > Comm Settings > Modbus Settings, and set Connection mode to
Server and client, Server encryption to Enable.
After the NetCol5000-A042 parameters are set, the ECC800-Pro can automatically identify the
automatic access of the NetCol5000-A042.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > Cooling > NetCol5000-A0421.
1 in NetCol5000-A0421 is variable and subject to change with the smart cooling product model and
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set running parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).