7.6 Control Management of the Infrared Remote Control
Module
In the FusionModule500 scenario, the civil smart cooling product can start automatically if
you enable the infrared remote control module on the ECC.

7.6.1 Connecting the Communications Cable

Procedure
Step 1 Use a communications cable to connect the T/H sensor to the COM2 port on the ECC800e.
Step 2 Use a communications cable to connect the infrared remote control module to the T/H sensor.
----End

7.6.2 Setting and Adding an Infrared Remote Control Module

Prerequisites
Context
If an infrared remote control module is replaced, you need to add the infrared remote control
module to the ECC800 WebUI.
Procedure
Step 1 Set monitoring parameters for the infrared remote control module.
1.
Table 7-2 Setting a device address
Address
1
2
Issue 02 (2019-02-28)
The infrared remote control module has connected to the ECC800e, and the infrared
remote control module and ECC800e are powered on.
You have obtained the IP address of the ECC800e as well as the user name and password
used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800e is
prepared, and the PC has connected to port WAN on the ECC800e.
Set the address to 1 by setting the DIP switch on the infrared remote control module.
Table 7-2 describes how to set the DIP switch.
The DIP switch consists of toggle switches 1-5 (from left to right). Toggle switches 1-4
specify the address of the infrared remote control module. Toggle switch 5 specifies the
address of the RS485 build-out resistor. 0 indicates OFF, and 1 indicates ON. The toggle
switch 5 is set to OFF.
Toggle
Switch 1
ON
OFF
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
7 Feature Description
Toggle
Switch 4
OFF
OFF