3.1
Electro-magnetic interference (EMI) and leakage
currents
3.1.1
Leakage currents and countermeasures
Capacitance exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current
flows. Since its value depends on the static capacitance, carrier frequency, etc., low acoustic noise operation at the increased
carrier frequency of the inverter will increase the leakage current. Therefore, take the following countermeasures. Select the
earth leakage current breaker according to its rated sensitivity current, independently of the carrier frequency setting.
 To-earth (ground) leakage currents
Leakage currents may flow not only into the inverter's own line but also into the other lines through the earthing (grounding)
cable, etc. These leakage currents may operate earth leakage circuit breakers and earth leakage relays unnecessarily.
 Countermeasures
• If the carrier frequency setting is high, decrease the Pr.72 PWM frequency selection setting. Note that motor noise
increases. Selecting Pr.240 Soft-PWM operation selection makes the sound inoffensive.
• By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other
line, operation can be performed with the carrier frequency kept high (with low noise).
NOTE
• Long wiring will increase the leakage current.
• High motor capacity will increase the leakage current.
 Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitance between the inverter output cables may operate the external
thermal relay unnecessarily. When the wiring length is long (50 m or more) for the 600 V class small-capacity models (FR-
F860-00170 or lower), the external thermal relay is likely to operate unnecessarily because the ratio of the leakage current to
the rated motor current increases.
 Line-to-line leakage current example (600 V class)
Motor capacity
Rated motor
(kW)
0.75
1.1
1.5
2.0
2.2
3.2
3.7
5.2
5.5
7.8
7.5
9.9
72
3. PRECAUTIONS FOR USE OF THE INVERTER

3.1 Electro-magnetic interference (EMI) and leakage currents

current (A)
Wiring length 50 m
1020
1110
1200
1320
1470
1605
MCCB
Power
supply
Line-to-line leakage currents path
Leakage current (mA)
Wiring length 100 m
1590
1680
1770
1890
2040
2175
MC
Thermal relay
Inverter/
converter
Condition
• Motor: 4P
• Carrier frequency: 14.5
kHz
2
• Cable: 2 mm
, 4 cores
• Cabtyre cable
Motor
M
Line-to-line static
capacitance