 Operation mode selection flow
Referring to the following table, select the basic parameter settings or terminal wiring related to the operation mode.
Start command
Frequency setting
input method
method
External signal
External (terminal 2
input
and 4, JOG, multi-
(terminal STF, STR)
speed, etc.)
PU (digital setting)
Communication
(RS-485 terminals)
Communication
(communication
option)
PU
External (terminal 2
(FWD/REV key)
and 4, JOG, multi-
speed, etc.)
PU (digital setting)
Communication (RS-
485 terminals/
communication option)
Communication
Using external signals
(RS-485 terminals)
(input via terminal 2/4,
using the JOG signal,
using the multi-speed
setting function, etc.)
PU (digital setting)
Communication
RS-485 terminals
Communication
Using external signals
(Communication
(input via terminal 2/4,
option)
using the JOG signal,
using the multi-speed
setting function, etc.)
PU (digital setting)
Communication
(communication
option)
Terminal wiring
STF (forward rotation)/STR
Pr.79 = "2"
(reverse rotation) (Refer to
(External operation
page
550.)
mode fixed)
Terminal 2 and 4 (analog)
RL, RM, RH, JOG, etc.
STF (forward rotation)/STR
Pr.79 = "3"
(reverse rotation) (Refer to
(External/PU
page
550.)
combined operation 1)
STF (forward rotation)/STR
Pr.338 = "1"
(reverse rotation) (Refer to
Pr.340 = "1, 2"
page
550.)
RS-485 terminals
(Refer to
page
475.)
Terminals for
Pr.338 = "1"
communication option
Pr.340 = "1"
(Refer to the Instruction
Manual of the
communication option.)
Terminal 2 and 4 (analog)
Pr.79 = "4"
RL, RM, RH, JOG, etc.
(External/PU
combined operation 2)
Pr.79 = "1"
(PU operation mode
fixed)
N/A
RS-485 terminals
Pr.339 = "1"
(Refer to
page
475.)
Pr.340 = "1, 2"
Terminal 2 and 4 (analog)
RL, RM, RH, JOG, etc.
N/A
RS-485 terminals
Pr.340 = "1, 2"
(Refer to
page
475.)
Terminals on communication
Pr.339 = "1"
option
Pr.340 = "1"
(Refer to the Instruction
Manual of the
communication option.)
Terminal 2 and 4 (analog)
RL, RM, RH, JOG, etc.
N/A
Terminals on communication
Pr.340 = "1"
option
(Refer to the Instruction
Manual of the
communication option.)
Parameter setting
Operation method
• Frequency setting
Frequency setting terminal ON
• Start command
STF(STR)-ON
• Frequency setting
DU digital setting
• Start command
STF(STR)-ON
• Frequency setting
Transmit a frequency command via
communication.
• Start command
STF(STR)-ON
• Frequency setting
Transmit a frequency command via
communication.
• Start command
STF(STR)-ON
• Frequency setting
Frequency setting terminal ON
• Start command
FWD/REV key ON
• Frequency setting
Digital setting
• Start command
FWD/REV key ON
• Frequency setting
Frequency setting terminal ON
• Start command
Transmit a start command via
communication
• Frequency setting
Transmit a frequency command via
communication.
• Start command
Transmit a start command via
communication
• Frequency setting
Frequency setting terminal ON
• Start command
Transmit a start command via
communication
• Frequency setting
Transmit a frequency command via
communication.
• Start command
Transmit a start command via
communication
5.6 (D) Operation command and frequency command
3
4
5
5
5
6
7
8
9
10
207
5. PARAMETERS