Mitsubishi Electric 800 Series Instruction Manual page 455

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.11.13 Offline auto tuning for a frequency search
V/F
V/F
V/F
During V/F control, the accuracy of the "frequency search", which is used to detect the motor speed for the automatic restart
after instantaneous power failure and flying start, can be improved.
Pr.
162
Automatic restart after
A700
instantaneous power failure
selection
298
Frequency search gain
A711
560
Second frequency search gain
A712
96
Auto tuning setting/status
C110
90
Motor constant (R1)
C120
463
Second motor auto tuning
C210
setting/status
458
Second motor constant (R1)
C220
*1
For the FR-F860-00680 or lower.
*2
For the FR-F860-01080 or higher.
*3
The same operation is performed for the both settings.
454
5. PARAMETERS
5.11 (A) Application parameters
Name
Initial
value
0
9999
9999
0
9999
0
9999
Setting range
Frequency search only performed at the first start
*3
0 (2)
,
*3
1000 (1002)
1, 1001
Reduced voltage start only at the first start
(no frequency search)
3, 1003
Frequency search only performed at the first start
(reduced impact restart)
Frequency search at every start
*3
10 (12)
,
*3
1010 (1012)
11, 1011
Reduced voltage start at every start (no frequency
search)
13, 1013
Frequency search at every start (reduced impact
restart)
0 to 32767
The offline auto tuning automatically sets the gain
required for the frequency search.
9999
Uses the constant value of standard motor.
0 to 32767
The offline auto tuning automatically sets the gain
required for the frequency search of the second motor.
9999
Uses the constant value of standard motor.
0
No offline auto tuning.
1, 101
Perform offline auto tuning for the Advanced magnetic
flux vector control. (Refer to
11
Performs offline auto tuning without rotating the motor
(V/F control).
Tuning data
*1
0 to 50 Ω, 9999
(The value measured by offline auto tuning is
*2
0 to 400 mΩ, 9999
automatically set.)
9999: Uses the constant value of standard motor.
0
No auto tuning for the second motor.
1, 101
Performs offline auto tuning for the second motor.
(Refer to
11
Performs offline auto tuning without rotating the
second motor (V/F control).
Tuning data of the second motor
*1
0 to 50 Ω, 9999
(same as Pr.90)
*2
0 to 400 mΩ, 9999
Description
page
353.)
page
353.)