• The following shows the relationship between the input values of the analog input terminals and set point, measured value
and deviation. (Calibration parameter initial values)
Input
Inspect
terminal
specification
Terminal 2
0 to 5 V
0 to 10 V
0 to 20 mA
Terminal 1
0 to ±5 V
0 to ±10 V
Terminal 4
0 to 5 V
0 to 10 V
0 to 20 mA
*6
Can be changed by Pr.73 and Pr.267 and the voltage/current input switch. (Refer to
NOTE
• Always perform calibration after changing the voltage/input specification with Pr.73, Pr.267, and the voltage/current input
selection switch.
 Multistage set point input (Pr.1460 to Pr.1466)
• The set point can be selected by combining the ON/OFF status of the PDI1 to PDI3 signals. Up to eight set points can be
selected. Use Pr.1460 PID multistage set point 1 to Pr.1466 PID multistage set point 7 to set the target values for
selection.
• When "9999" is set in the selected multistage set point parameter, PID control is performed according to the Pr.128,
Pr.609, and Pr.133 settings.
Selected set point
Multistage set point 1
Multistage set point 2
Multistage set point 3
Multistage set point 4
Multistage set point 5
Multistage set point 6
Multistage set point 7
*1
When functions are not assigned to the input terminals, the signals are treated as OFF.
NOTE
• The multistage set point input is not available for the second PID.
• The priority of the set point input is as follows: Pr.1460 to Pr.1466 > Pr.133 > Pr.128.
404
5. PARAMETERS
5.11 (A) Application parameters
Relationship with analog input
*6
Set point
0 V=0%
5 V=100%
0 V=0%
10 V=100%
0 mA=0%
20 mA=100%
-5 V to 0 V=0%
5 V=+100%
-10 V to 0 V=0%
10 V=+100%
0 V to 1 V=0%
5 V=100%
0 V to 2 V=0%
10 V=100%
0 to 4 mA=0%
20 mA=100%
*1
*1
PDI1
PDI2
PDI3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
Result
0 V=0%
0 V=0%
5 V=100%
5 V=100%
0 V=0%
0 V=0%
10 V=100%
10 V=100%
0 mA=0%
0 V=0%
20 mA=100%
20 mA=100%
-5 V to 0 V=0%
-5 V=-100%
5 V=+100%
0 V=0%
5 V=+100%
-10 V to 0 V=0%
-10 V=-100%
10 V=+100%
0 V=0%
10 V=+100%
0 Vto 1 V=0%
0 V=-20%
5 V=100%
1 V=0%
5 V=100%
0 V to 2 V=0%
0 V=-20%
10 V=100%
1 V=0%
10 V=100%
0 to 4 mA=0%
0 V=-20%
20 mA=100%
4 mA=0%
20 mA=100%
page
*1
Parameter for setting
As set in the Pr.128 and Pr.609 PID settings.
As set Pr.133 when Pr.133"9999".
Pr.1460
Pr.1461
Pr.1462
Pr.1463
Pr.1464
Pr.1465
Pr.1466
Calibration parameter
Deviation
Pr.125, C2 to C4
When Pr.128 = "10",
Pr.125, C2 to C4.
When Pr.128  "1000",
C12 to C15.
Pr.126, C5 to C7
318.)