• The following shows the relationship between the input values of the analog input terminals and set point, measured value
and deviation. (Calibration parameter initial values)
Input
Inspect
terminal
specification
Terminal 2
0 to 5 V
0 to 10 V
0 to 20 mA
Terminal 1
0 to ±5 V
0 to ±10 V
Terminal 4
0 to 5 V
0 to 10 V
0 to 20 mA
*6
Can be changed by Pr.73 and Pr.267 and the voltage/current input switch. (Refer to
NOTE
• Always perform calibration after changing the voltage/input specification with Pr.73, Pr.267, and the voltage/current input
selection switch.
Multistage set point input (Pr.1460 to Pr.1466)
• The set point can be selected by combining the ON/OFF status of the PDI1 to PDI3 signals. Up to eight set points can be
selected. Use Pr.1460 PID multistage set point 1 to Pr.1466 PID multistage set point 7 to set the target values for
selection.
• When "9999" is set in the selected multistage set point parameter, PID control is performed according to the Pr.128,
Pr.609, and Pr.133 settings.
Selected set point
―
Multistage set point 1
Multistage set point 2
Multistage set point 3
Multistage set point 4
Multistage set point 5
Multistage set point 6
Multistage set point 7
*1
When functions are not assigned to the input terminals, the signals are treated as OFF.
NOTE
• The multistage set point input is not available for the second PID.
• The priority of the set point input is as follows: Pr.1460 to Pr.1466 > Pr.133 > Pr.128.
404
5. PARAMETERS
5.11 (A) Application parameters
Relationship with analog input
*6
Set point
0 V=0%
5 V=100%
0 V=0%
10 V=100%
0 mA=0%
20 mA=100%
-5 V to 0 V=0%
5 V=+100%
-10 V to 0 V=0%
10 V=+100%
0 V to 1 V=0%
5 V=100%
0 V to 2 V=0%
10 V=100%
0 to 4 mA=0%
20 mA=100%
*1
*1
PDI1
PDI2
PDI3
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
Result
0 V=0%
0 V=0%
5 V=100%
5 V=100%
0 V=0%
0 V=0%
10 V=100%
10 V=100%
0 mA=0%
0 V=0%
20 mA=100%
20 mA=100%
-5 V to 0 V=0%
-5 V=-100%
5 V=+100%
0 V=0%
5 V=+100%
-10 V to 0 V=0%
-10 V=-100%
10 V=+100%
0 V=0%
10 V=+100%
0 Vto 1 V=0%
0 V=-20%
5 V=100%
1 V=0%
5 V=100%
0 V to 2 V=0%
0 V=-20%
10 V=100%
1 V=0%
10 V=100%
0 to 4 mA=0%
0 V=-20%
20 mA=100%
4 mA=0%
20 mA=100%
page
*1
Parameter for setting
As set in the Pr.128 and Pr.609 PID settings.
As set Pr.133 when Pr.133"9999".
Pr.1460
Pr.1461
Pr.1462
Pr.1463
Pr.1464
Pr.1465
Pr.1466
Calibration parameter
Deviation
Pr.125, C2 to C4
When Pr.128 = "10",
Pr.125, C2 to C4.
When Pr.128 "1000",
C12 to C15.
Pr.126, C5 to C7
318.)