5.12.7
BACnet MS/TP protocol
Using BACnet MS/TP protocol, communication operation and parameter setting are available from the RS-485 terminals of the
inverter.
Pr.
Name
52
Operation panel main
M100
monitor selection
774
Second motor inertia
M101
(integer)
775
Second motor inertia
M102
(exponent)
776
Second motor
M103
protection current level
331
RS-485 communication
N030
station number
332
RS-485 communication
N031
speed
390
% setting reference
N054
frequency
549
Protocol selection
N000
726
Auto Baudrate/Max
N050
Master
727
Max Info Frames
N051
728
Device instance
N052
number (Upper 3
digits)
729
Device instance
N053
number (Lower 4
digits)
*1
When the set value is outside of the setting range, the initial value is applied.
*2
When the Auto baudrate is used, the communication speed is changed to the detected communication speed.
516
5. PARAMETERS
5.12 (N) Operation via communication and its settings
Initial value
Setting range
0
0, 5 to 14, 17, 18, 20,
23 to 25, 34, 38, 40
to 45, 50 to 57, 61,
62, 64, 67 to 69, 81
to 96, 98, 100
9999
1 to 3, 5 to 14, 17,
18, 20, 23 to 25, 34,
38, 40 to 45,
50 to 57, 61, 62, 64,
67 to 69, 81 to 96,
98, 100
0
*1
0 to 127
96
96, 192, 384, 576,
*1*2
768, 1152
60 Hz
1 to 590 Hz
0
0
1
2
255
0 to 255
1
1 to 255
0
0 to 419
(0 to 418)
0
0 to 9999
(0 to 4302)
Description
81: BACnet reception status
82: BACnet token pass counter (Displays the count of
received token)
83: BACnet valid APDU counter (Displays the count of valid
APDU detection)
84: BACnet communication error counter (Displays the count
of communication error)
85: Terminal CA output level (Same display as Analog Output
0)
86: Terminal AM output level (Same display as Analog Output
1)
The count of the setting values "82" and "83" returns to "0" if
the count exceeds "9999". The upper limit of the count of the
setting value "84" is "9999".
Set the inverter station number (node).
Set the communication speed.
The setting value  100 equals the communication speed.
For example, the communication speed is 9600 bps when the
setting value is "96".
Set a reference frequency of the set frequency.
Mitsubishi inverter (computer link) protocol
MODBUS RTU protocol
BACnet MS/TP protocol
Auto baud rate (bit 7)
0: inactive, 1: active
Max Master (bit 0 to bit 6) setting range: 0 to 127
Maximum address for master node
Set the maximum number of frames that the inverter can
transmit while it owns the token.
Device identifier
When the combination of Pr.728 and Pr.729 is not within "0 to
4194302", the setting is out of range.
When Pr.728="419", the setting range of Pr.729 is "0 to 4302".
When Pr.729="4303" or more, the setting range of Pr.728 is
"0 to 418".