Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current
flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the increased
carrier frequency of the inverter will increase the leakage current. Therefore, take the following countermeasures. Select the
earth leakage current breaker according to its rated sensitivity current, independently of the carrier frequency setting.
 To-earth (ground) leakage currents
Leakage currents may flow not only into the inverter's own line but also into the other lines through the earthing (grounding)
cable, etc. These leakage currents may operate earth leakage circuit breakers and earth leakage relays unnecessarily.
 Countermeasures
• If the carrier frequency setting is high, decrease the Pr.72 PWM frequency selection setting.
Note that motor noise increases. Selecting Pr.240 Soft-PWM operation selection makes the sound inoffensive.
• By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other
line, operation can be performed with the carrier frequency kept high (with low noise).
 To-earth (ground) leakage currents
• Take caution as long wiring will increase the leakage current. Decreasing the carrier frequency of the inverter reduces the
leakage current.
• High motor capacity will increase the leakage current.
 Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external
thermal relay unnecessarily.
Power
supply
 Countermeasures
• Use Pr.9 Electronic thermal O/L relay.
• If the carrier frequency setting is high, decrease the Pr.72 PWM frequency selection setting.
Note that motor noise increases. Selecting Pr.240 Soft-PWM operation selection makes the sound inoffensive.
To ensure that the motor is protected against line-to-line leakage currents, it is recommended to use a temperature sensor
to directly detect motor temperature.
70
3. PRECAUTIONS FOR USE OF THE INVERTER

3.1 Electro-magnetic interference (EMI) and leakage currents

MCCB
MC
Converter
Line-to-line leakage currents path
Thermal relay
Inverter
unit
Motor
M
Line-to-line static
capacitances

Advertisement

Table of Contents
loading

Table of Contents