• To enable the self power management function for the separated converter type, enable the self power management
function also on the converter unit side. To activate the self power management function when a converter unit fault occurs,
connect the terminal to which Y17 signal of the converter unit is assigned and the terminal to which X94 signal of the
inverter is assigned.
Y17 output signal (on the
converter unit side)
OFF
OFF
ON
ON
NOTE
• When the start signal is turned OFF before the time set in Pr.137 has passed after the start signal is turned ON, the inverter
does not start and the MC1 signal is turned OFF after the time set in Pr.254 has passed. If the start signal is turned ON
again before the time set in Pr.254 has passed, the inverter immediately starts outputting.
Output frequency
(Hz)
STF
MC1
• At inverter reset, the status of the MC1 signal is held and operation of the magnetic contactor is not performed.
• When the inverter stops the output due to, for example, the Output stop (MRS) signal, the MC1 signal is turned OFF after
the time set in Pr.254 has passed.
• During the stop, turning ON the External DC injection brake operation start signal (X13) turns ON the MC1 signal.
• To avoid inverter reset when starting to supply power to the main circuit when power is already supplied only to the control
circuit, set 100 or more in Pr.30. (For the separated converter type, setting Pr.30 of the converter unit is also required.)
• When supplying power to the main circuit is started when power is supplied only to the control circuit, there is a little waiting
time before starting.
• Repeated operation of the magnetic contactor due to frequent start and stop or activation of the protective function may
shorten the inverter life.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) and Pr.190 to Pr.196
(Output terminal function selection) may affect the other functions. Set parameters after confirming the function of each
terminal.
Parameters referred to
Pr.11 DC injection brake operation time
Pr.30 Regenerative function selection
Pr.190 to Pr.196 (Output terminal function selection)
MC1 output signal
MC1 output signal actual
(inverter side)
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
Time
ON
OFF
ON
OFF
Pr.137
Pr.254
page 546
page 553
page 297
Main circuit power supply
operation
Stop
Stop
Stop
Supplied
Output frequency
(Hz)
ON
OFF
STF
ON
MC1
Pr.137
Time
ON
Pr.254
5. PARAMETERS
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10
387