5.7.12
Stall prevention operation
This function monitors the output current and automatically changes the output frequency to prevent the inverter from tripping
due to overcurrent, overvoltage, etc. It can also limit the stall prevention and fast-response current limit operation during
acceleration/deceleration and power/regenerative driving.
• Stall prevention
If the output current exceeds the stall prevention operation level, the output frequency of the inverter is automatically changed
to reduce the output current.
Also the second stall prevention function can limit the output frequency range in which the stall prevention function is enabled.
• Fast-response current limit
If the current exceeds the limit value, the output of the inverter is shut off to prevent an overcurrent.
Pr.
Name
22
Stall prevention operation
H500
level
156
Stall prevention operation
H501
selection
48
Second stall prevention
H600
operation level
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
49
Second stall prevention
H601
operation frequency
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
23
Stall prevention operation
H610
level compensation factor at
double speed
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
66
Stall prevention operation
H611
reduction starting frequency
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
148
Stall prevention level at 0 V
H620
input
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
149
Stall prevention level at 10 V
H621
input
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
154
Voltage reduction selection
H631
during stall prevention
operation
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
157
OL signal output timer
M430
858
Terminal 4 function
T040
assignment
868
Terminal 1 function
T010
assignment
874
OLT level setting
H730
PM
PM
PM
Initial
Setting range
value
110%
0
*1
0.1 to 400%
0
0 to 31, 100 to 101
110%
0
*1
0.1 to 400%
0 Hz
0
0.01 to 590 Hz
9999
9999
0 to 200%
9999
60 Hz
0 to 590 Hz
110%
*1
0 to 400%
120%
*1
0 to 400%
1
0
1
10
11
0 s
0 to 25 s
9999
0
0, 4, 9999
0
0, 4, 9999
110%
0 to 400%
Description
Stall prevention operation disabled.
Set the current limit at which the stall prevention operation
will start.
Enable/disable the stall prevention operation and the fast-
response current limit operation.
Second stall prevention operation disabled.
The stall prevention operation level can be changed using
the RT signal.
Second stall prevention operation disabled.
Set the frequency at which the Pr.48 stall prevention
operation will start.
Pr.48 is enabled when RT signal is ON.
The stall operation level when running at high speeds
above the rated frequency can be reduced.
Stall prevention operation disabled at double speed.
Set the frequency at which the stall operation level
reduction will start.
The stall prevention operation level can be changed by the
analog signal input to the terminal 1 (terminal 4).
Output voltage
Enable/disable the output voltage
reduction enabled.
reduction during stall prevention
operation.
Output voltage
reduction disabled.
Output voltage
Use this setting when the
reduction enabled.
overvoltage protective function
(E.OV[ ]) activates during stall
Output voltage
prevention operation in an
reduction disabled.
application with large load inertia.
Set the OL signal output start time when stall prevention is
activated.
No OL signal output.
When set "4", the stall prevention level can be changed
with the signal to the terminal 4.
When set "4", the stall prevention level can be changed
with the signal to the terminal 1.
A trip can be set for when the stall prevention is activated
and the motor stalls. Set the output at which to activate the
trip.
5.7 (H) Protective function parameter
3
4
5
5
5
6
7
8
9
10
257