5.8.6
Output terminal function selection
Use the following parameters to change the functions of the open collector output terminals and relay output terminals.
Pr.
Name
190
RUN terminal function
M400
selection
191
SU terminal function
M401
selection
192
IPF terminal function
M402
selection
193
OL terminal function
M403
selection
194
FU terminal function
M404
selection
195
ABC1 terminal function
M405
selection
196
ABC2 terminal function
M406
selection
*3
DO0 output selection
313
M410
DO1 output selection
*3
314
M411
DO2 output selection
*3
315
M412
DO3 output selection
*3
316
M413
DO4 output selection
*3
317
M414
DO5 output selection
*3
318
M415
DO6 output selection
*3
319
M416
*3
RA1 output selection
320
M420
RA2 output selection
*3
321
M421
*3
RA3 output selection
322
M422
Pr.
Name
289
Inverter output terminal
M431
filter
*1
The initial value is for standard models.
*2
The initial value is for separated converter types.
*3
The setting is available when the PLC function is enabled.
Initial
Initial set signal
value
Open
0
RUN (Inverter running)
collector
output
1
SU (Up to frequency)
terminal
IPF (Instantaneous power
*1
2
failure/undervoltage)
No function
*2
9999
3
OL (Overload warning)
4
FU (Output frequency
detection)
Relay
99
ALM (Fault)
output
terminal
9999
No function
For
9999
No function
terminal
on the
9999
No function
option
9999
No function
9999
No function
9999
No function
9999
No function
9999
No function
0
RUN (Inverter running)
1
SU (Up to frequency)
*1
IPF (Instantaneous power
2
failure/undervoltage)
*2
No function
9999
Initial value
Setting range
9999
5 to 50 ms
9999
Setting range
0 to 5, 7, 8, 10 to 19, 23, 25, 26, 35, 39 to
42, 45 to 54, 57, 64 to 68, 70 to 80, 82, 85,
90 to 96, 98 to 105, 107, 108, 110 to 116,
123, 125, 126, 135, 139 to 142, 145 to 154,
157, 164 to 168, 170 to 180, 182, 185, 190
to 196, 198 to 208, 211 to 213, 215, 217 to
220, 226, 228 to 230, 247, 300 to 308, 311
to 313, 315, 317 to 320, 326, 328 to 330,
347, 9999
0 to 5, 7, 8, 10 to 19, 23, 25, 26, 35, 39 to
42, 45 to 54, 57, 64 to 68, 70 to 80, 82, 85,
90, 91, 94 to 96, 98 to 105, 107, 108, 110 to
116, 123, 125, 126, 135, 139 to 142, 145 to
154, 157, 164 to 168, 170 to 180, 182, 185,
190, 191, 194 to 196, 198 to 208, 211 to
213, 215, 217 to 220, 226, 228 to 230, 247,
300 to 308, 311 to 313, 315, 317 to 320,
326, 328 to 330, 347, 9999
0 to 5, 7, 8, 10 to 19, 23, 25, 26, 35, 39 to
42, 45 to 54, 57, 64 to 66, 68, 70 to 80, 85
to 96, 98 to 105, 107, 108, 110 to 116, 123,
125, 126, 135, 139 to 142, 145 to 154, 157,
164 to 166, 168, 170 to 180, 185 to 196,
198 to 208, 211 to 213, 215, 217 to 220,
226, 228 to 230, 247 to 250, 300 to 308,
311 to 313, 315, 317 to 320, 326, 328 to
330, 347 to 350, 9999
0 to 5, 7, 8, 10 to 19, 23, 25, 26, 35, 39 to
42, 45 to 54, 57, 64 to 66, 68, 70 to 80, 85
to 91, 94 to 96, 98, 99, 200 to 208, 211 to
213, 215, 217 to 220, 226, 228 to 230, 247
to 250, 9999
Description
Set the time delay for the output terminal response.
No output terminal filter.
5.8 (M) Monitor display and monitor output signal
3
4
5
5
5
6
7
8
9
10
297
5. PARAMETERS