NOTE
• When the power is supplied to the main circuit while the inverter protective function is activated, the inverter reset is
performed even if it the setting is "No reset" at power ON.
 DC feeding mode 1 (Pr.30 = "10") (Standard models)
• For standard models, setting Pr.30 = "10" allows operation with a DC power supply.
• Do not connect anything to the AC power supply connecting terminals R/L1, S/L2, and T/L3, and connect the DC power
supply to the terminals P/+ and N/-. Also, remove the jumpers between terminal R/L1 and R/L11as well as between S/L2
and S1/L21, and connect the terminals R1/L11 and S1/L21 to the terminals P/+ and N/-.
• Following is a connection example.
DC power
Frequency command
Frequency setting
potentiometer
CAUTION
• Do not connect a separated converter type inverter to a DC power supply. Doing so may damage the inverter.
 DC feeding mode 2 (Pr.30 = "20") (Standard models)
• When Pr.30 = "20", it will normally operate with AC power supply and operate with DC power supply such as batteries at
the time of power failure.
• Connect the AC power supply to the AC power supply connecting terminals R/L1, S/L2, and T/L3, and connect the DC
power supply to the terminals P/+ and N/-. Also, remove the jumpers between terminal R/L1 and R/L11as well as between
S/L2 and S1/L21, and connect the terminals R1/L11 and S1/L21 to the terminals P/+ and N/-.
• Operation with DC current is possible by turning ON the DC feeding operation permission signal (X70). For details on I/O
signal, refer to following table.
Signal
Name
name
X70
DC feeding
To operate with DC feeding, turn ON the X70 signal. When the inverter output is shutoff
operation
due to power failure, it will be possible to start up 200 ms after turning ON the X70 signal.
permission
(Automatic restart after instantaneous power failure can start after the time set in Pr.57 has
signal
elapsed.)
When the X70 signal is turned OFF while operating the inverter, output shutoff (Pr.261 =
0) or deceleration stop (Pr.261 ≠ 0) will occur.
X71
DC feeding
Turn ON when stopping the DC feeding. When the X71 signal is turned ON during the
cancel signal
operation of the inverter and X70 signal is ON, output shutoff (Pr.261 = 0) or deceleration
stop (Pr.261 ≠ 0) will occur, and Y85 signal will turn OFF after stopping. After turning ON
the X71 signal, operation is not possible even if the X70 signal is turned ON.
Y85
DC feeding
This will turn ON during power failure or undervoltage of the AC power supply. It will turn
signal
OFF when the X71 signal turns ON or power restoration.
The Y85 signal will not turn OFF even with the power restoration while the inverter is
running, but turns OFF after stopping the inverter. When the Y85 signal is turned ON due
to undervoltage, the Y85 signal will not turn OFF even when the undervoltage is resolved.
The ON/OFF status is maintained when the inverter is reset.
MC
(+)
(-)
Forward rotation start
Reverse rotation start
Contact input common
3
2
1
1/2 W 1 k:
Inverter
Inrush
R/L1
U
current
limit circuit
S/L2
V
W
T/L3
R1/L11
S1/L21
P/+
N/-
STF
STR
SD
10
2
5
Description
M
Earth
(Ground)
Parameter
setting
Set "70" to either
of Pr.178 to
Pr.189.
Set "71" to either
of Pr.178 to
Pr.189.
Set "85 (positive
logic) or 185
(negative logic)"
to one of Pr.190
to Pr.196.
5. PARAMETERS
5.13 (G) Control parameters
3
4
5
5
5
6
7
8
9
10
555