Mitsubishi Electric 800 Series Instruction Manual page 127

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Function
Pr.
Additional
849
function
858
859
860
864
Indication
866
function
867
868
869
870
Protective
872
Functions
*7
874
Regeneration
882
avoidance
function
883
884
885
886
Free
888
parameters
889
890
Energy saving
891
monitor
892
893
894
895
896
897
898
899
126
5. PARAMETERS
5.1 Parameter List
Pr.
Name
group
T007
Analog input offset
adjustment
T040
Terminal 4 function
assignment
C126
Torque current/Rated
PM motor current
C226
Second motor torque
current/Rated PM motor
current
M470
Torque detection
M042
Torque monitoring
reference
M321
AM output filter
T010
Terminal 1 function
assignment
M334
Current output filter
M440
Speed detection
hysteresis
H201
Input phase loss
protection selection
H730
OLT level setting
G120
Regeneration avoidance
operation selection
G121
Regeneration avoidance
operation level
G122
Regeneration avoidance
at deceleration detection
sensitivity
G123
Regeneration avoidance
compensation
frequency limit value
G124
Regeneration avoidance
voltage gain
E420
Free parameter 1
E421
Free parameter 2
H325
Internal storage device
status indication
M023
Cumulative power
monitor digit shifted
times
M200
Load factor
M201
Energy saving monitor
reference (motor
capacity)
M202
Control selection during
commercial power-
supply operation
M203
Power saving rate
reference value
M204
Power unit cost
M205
Power saving monitor
average time
M206
Power saving
cumulative monitor clear
M207
Operation time rate
(estimated value)
Setting range
Minimum
setting
increments
0 to 200%
0.1%
0, 4, 9999
1
*2
0 to 500 A, 9999
0.01 A
*3
0 to 3600 A, 9999
0.1 A
*2
0 to 500 A, 9999
0.01 A
*3
0 to 3600 A, 9999
0.1 A
0 to 400%
0.1%
0 to 400%
0.1%
0 to 5 s
0.01 s
0, 4, 9999
1
0 to 5 s
0.01 s
0 to 5 Hz
0.01 Hz
0, 1
1
0 to 400%
0.1%
0 to 2
1
300 to 1200 V
0.1 V
0 to 5
1
0 to 590 Hz, 9999
0.01 Hz
0 to 200%
0.1%
0 to 9999
1
0 to 9999
1
(0 to 511)
1
0 to 4, 9999
1
30 to 150%
0.1%
*2
0.1 to 55 kW
0.01 kW
*3
0 to 3600 kW
0.1 kW
0 to 3
1
0, 1, 9999
1
0 to 500, 9999
0.01
0 to 1000 h, 9999
1 h
0, 1, 10, 9999
1
0 to 100%, 9999
0.1%
Initial value
Refer
to
page
100%
326
0
257,
322
*2
9999
353,
363
*3
*2
9999
353,
363
*3
150%
309
150%
284
0.01 s
288
0
257,
322
0.02 s
288
0 Hz
305
0
241
110%
257
0
559
940 V
559
0
559
6 Hz
559
100%
559
9999
172
9999
172
0
253
9999
274,
291
100%
291
Inverter
291
*2
capacity
*3
0
291
9999
291
9999
291
9999
291
9999
291
9999
291
Customer
setting