Pr.
Name
609
PID set point/deviation
A624
input selection
610
PID measured value input
A625
selection
1015
Integral stop selection at
A607
limited frequency
1346
PID lower limit operation
A457
detection time
1370
Detection time for PID
A442
limiting operation
1460
PID multistage set point 1
A683
1461
PID multistage set point 2
A684
1462
PID multistage set point 3
A685
1463
PID multistage set point 4
A686
1464
PID multistage set point 5
A687
1465
PID multistage set point 6
A688
1466
PID multistage set point 7
A689
Initial value
Setting range
2
1
2
3
4
5
3
1
2
3
4
5
101
102
103
104
105
0
0
1
2
10
11
12
9999
0 to 900 s
9999
0 s
0 to 900 s
9999
0 to 100%
Description
Input of set point, deviation value from terminal 1
Input of set point, deviation value from terminal 2
Input of set point, deviation value from terminal 4
Input of set point, deviation value via communication
Input of set point, deviation value by PLC function
Terminal 1 input
Direct input of the measured value
Terminal 2 input
Terminal 4 input
Communication
input
PLC function input
Terminal 1 input
Input of the square root of the
measured value
Terminal 2 input
Terminal 4 input
Communication
input
PLC function input
Integral stopped at the limit, manipulation range of ±100%,
integral cleared during output interruption
Integral continued at the limit, manipulation range of ±100%,
integral cleared during output interruption
Integral stopped at the limit, manipulation range of 0 to
100%, integral cleared during output interruption
Integral stopped at the limit, manipulation range of ±100%,
integral stopped during output interruption
Integral continued at the limit, manipulation range of ±100%,
integral stopped during output interruption
Integral stopped at the limit, manipulation range of 0 to
100%, integral stopped during output interruption
Set the time from when the measured value input falls below
the Pr.132 setting until the FDN signal is output.
As set in Pr.1370.
Set the time from when the measured value input exceeds
the Pr.131 or Pr.132 setting until the FUP or FDN signal is
output.
Seven set points can be set according to the combination of
the PDI1, PDI2, and PDI3 signals.
9999: Not selected
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10
397
5. PARAMETERS