 Inverter operation ready signals (RY signal) and inverter running signals
(RUN, RUN3 signals)
• When the inverter is ready for operation, the Inverter operation ready (RY) signal turns ON (and stays ON during
operation).
• When the inverter output frequency reaches Pr.13 Starting frequency or higher, the Inverter running (RUN) signals turn
ON. The signal is OFF while the inverter is stopped and during DC injection brake operation. Inverter
• The Inverter running and start command is ON (RUN3) signal is ON while the inverter is running or the start signal is ON.
(When the start command is ON, the RUN3 signal output turns ON even while the inverter's protective function is activated
or the MRS is ON.) During DC injection brake operation as well, the output is ON, and when the inverter stops, it turns OFF.
Power
ON
supply
ON
STF
ON
RH
Pr. 13
Reset
processing
ON
RY
ON
RUN
ON
RUN3
• According to the inverter condition, the ON/OFF operation of each signal is as shown below.
Output
Start signal
signal
OFF
(during stop)
ON
*3
RY
RUN
OFF
RUN3
OFF
*1
OFF during power failure or undervoltage.
*2
Output is shutoff in conditions like a fault and when the MRS signal is ON.
*3
OFF while power is not supplied to the main circuit power supply.
• When using the RY, RUN and RUN3 signals, refer to the following and assign the functions by Pr.190 to Pr.196 (Output
terminal function selection).
Output signal
Pr.190 to Pr.196 settings
Positive logic
RY
11
RUN
0
RUN3
45
NOTE
• The RUN signal (positive logic) is assigned to the terminal RUN in the initial status.
OFF
OFF
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
OFF
OFF
Start signal
Start signal
ON
ON
(during stop)
(running)
ON
ON
OFF
ON
ON
ON
Negative logic
111
100
145
DC
Output shutoff
injection
brake
operation
Start
Start
signal
signal
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
5.8 (M) Monitor display and monitor output signal
*2
Automatic restart after
instantaneous power failure
Coasting
Restarting
Start
Start
signal
signal
ON
OFF
ON
*1
ON
OFF
ON
ON
OFF
ON
5. PARAMETERS
3
4
5
5
5
6
7
8
9
10
303

Advertisement

Table of Contents
loading

Table of Contents