 Setting multiple PID pre-charge functions
• When the second pre-charge function is set, two sets of pre-charge functions can be switched for use. The second pre-
charge function is enabled by turning ON the RT signal.
• The second pre-charge function parameters and signals function in the same way as the following parameters and signals
of the first pre-charge function. Refer to the first pre-charge function when setting the second pre-charge functions.
Classification
Parameter
Classification
Input signal
Output signal
NOTE
• The second PID pre-charge function is valid also when the first pre-charge function is set to invalid and the second pre-
charge function is set.
• When "10" (second function enabled only during constant-speed operation) is set to Pr.155, the second PID function is not
selected even if the RT signal turns ON.
428
5. PARAMETERS
5.11 (A) Application parameters
First pre-charge function parameters
Pr.
Name
760
Pre-charge fault selection
761
Pre-charge ending level
762
Pre-charge ending time
763
Pre-charge upper detection level
764
Pre-charge time limit
1132
Pre-charge change increment amount
First pre-charge function parameters
Signal
Name
X77
Pre-charge end command
Y49
During pre-charge operation
Y51
Pre-charge time over
Y53
Pre-charge level over
Second pre-charge function parameters
Pr.
Name
765
Second pre-charge fault selection
766
Second pre-charge ending level
767
Second pre-charge ending time
768
Second pre-charge upper detection
level
769
Second pre-charge time limit
1133
Second pre-charge change increment
amount
Second pre-charge function parameters
Signal
Name
X78
Second pre-charge end command
Y50
During second pre-charge operation
Y52
Second pre-charge time over
Y54
Second pre-charge level over