5.4.2
Reset selection / disconnected PU detection / PU stop
selection
The reset input acceptance, disconnected PU (operation panel/parameter unit) connector detection function and PU stop
function (PU stop) can be selected.
Pr.
75
Reset selection/disconnected
PU detection/PU stop selection
E100
Reset selection
E101
Disconnected PU detection
E102
PU stop selection
E107
Reset limit
The parameters above will not return to their initial values even if parameter (all) clear is executed.
*1
The setting range for the FR-F860-00680 or lower.
*2
The setting range for the FR-F860-01080 or higher.
Pr.75 setting
0
Always enabled.
1
When the protective function is activated.
2
Always enabled.
3
When the protective function is activated.
14 (initial
Always enabled.
value)
15
When the protective function is activated.
16
Always enabled.
17
When the protective function is activated.
100
Always enabled.
101
When the protective function is activated.
102
Always enabled.
103
When the protective function is activated.
114
Always enabled.
115
When the protective function is activated.
116
Always enabled.
117
When the protective function is activated.
162
5. PARAMETERS
5.4 (E) Environment setting parameters
Name
Initial value
14
0
0
1
0
Reset input
Setting range
0 to 3, 14 to 17, 1000 to
*1
1003, 1014 to 1017
0 to 3, 14 to 17, 100 to
103, 114 to 117, 1000 to
1003, 1014 to 1017, 1100
*2
to 1103, 1114 to 1117
0
1
2
3
0
1
0
1
0
*2
1
Operation after PU
disconnection is
detected
Operation continues.
Disabled
Inverter output shutoff
Operation continues.
Enabled
Inverter output shutoff
Operation continues.
Disabled
Inverter output shutoff
Operation continues.
Enabled
Inverter output shutoff
Description
For the initial setting, reset is always enabled,
without disconnected PU detection, and with
the PU stop function.
Reset input is always enabled.
Reset input is enabled only when the
protective function is activated.
Reset input is enabled only when the start
signal is OFF.
Reset input is enabled when the protective
function is activated and the start signal is
OFF.
Operation continues even when the PU is
disconnected.
The inverter output is shut off when the PU is
disconnected.
Decelerates to a stop when the STOP key is
pressed in PU operation mode only.
Decelerates to a stop when the STOP key for
PU is pressed in any of the PU, external and
communication operation modes.
Reset limit disabled
Reset limit enabled
PU stop function
Disabled
Enabled
Reset limit
function
*3