Reset limit function (P.E107)
• When P.E107 = "1" or Pr.75 = any of "100 to 103 and 114 to 117", if an electronic thermal O/L relay or an overcurrent
protective function (E.THM, E.THT, E.OC[]) is activated while one of them has been already activated within 3 minutes,
the inverter will not accept any reset command (RES signal, etc.) for about 3 minutes from the second activation.
• The reset limit function is available with the FR-F860-01080 or higher.
NOTE
• Resetting the inverter power (turning OFF the control power) will clear the accumulated thermal value.
• When the retry function is set enabled (Pr.67 Number of retries at fault occurrence "0"), the reset limit function is
disabled.
CAUTION
• Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the motor, which is dangerous.
Parameters referred to
Pr.67 Number of retries at fault occurrence
Pr.79 Operation mode selection
page 550
Pr.250 Stop selection
Pr.551 PU mode operation command source selection
5.4.3
PU display language selection
The display language of the parameter unit (FR-PU07) can be selected.
Pr.
Name
145
PU display language selection
E103
5.4.4
Buzzer control
The PU (operation panel or parameter unit) key sound and buzzer can be turned ON/OFF.
Pr.
Name
990
PU buzzer control
E104
NOTE
• When the buzzer is set to ON, a warning sound will be audible when a fault occurs.
5.4.5
PU contrast adjustment
Contrast adjustment of the LCD of the LCD operation panel (FR-LU08) and the parameter unit (FR-PU07) can be performed.
Decreasing the setting value lowers the contrast.
Pr.
Name
991
PU contrast adjustment
E105
The above parameter is displayed as a simple mode parameter only when the LCD operation panel (FR-LU08) and the
parameter unit (FR-PU07) are connected.
page 242
page 204
page 214
Initial value
—
Initial value
1
Initial value
58
Setting range
0
Japanese
1
English
2
German
3
French
4
Spanish
5
Italian
6
Swedish
7
Finnish
Setting range
0
Turns the key sound and buzzer OFF.
1
Turns the key sound and buzzer ON.
Setting range
0: Low 63: High
0 to 63
5.4 (E) Environment setting parameters
Description
Description
Description
165
5. PARAMETERS
3
4
5
5
5
6
7
8
9
10