• When P.E107 = "1" or Pr.75 = any of "100 to 103 and 114 to 117", if an electronic thermal O/L relay or an overcurrent
protective function (E.THM, E.THT, E.OC[]) is activated while one of them has been already activated within 3 minutes,
the inverter will not accept any reset command (RES signal, etc.) for about 3 minutes from the second activation.
• The reset limit function is available with the FR-F860-01080 or higher.
NOTE
• Resetting the inverter power (turning OFF the control power) will clear the accumulated thermal value.
• When the retry function is set enabled (Pr.67 Number of retries at fault occurrence  "0"), the reset limit function is
disabled.
CAUTION
• Do not perform a reset while a start signal is being input. Doing so will cause a sudden start of the motor, which is dangerous.
Parameters referred to
Pr.67 Number of retries at fault occurrence
Pr.79 Operation mode selection
page 550
Pr.250 Stop selection
Pr.551 PU mode operation command source selection
5.4.3
PU display language selection
The display language of the parameter unit (FR-PU07) can be selected.
Pr.
Name
145
PU display language selection
E103
5.4.4
Buzzer control
The PU (operation panel or parameter unit) key sound and buzzer can be turned ON/OFF.
Pr.
Name
990
PU buzzer control
E104
NOTE
• When the buzzer is set to ON, a warning sound will be audible when a fault occurs.
5.4.5
PU contrast adjustment
Contrast adjustment of the LCD of the LCD operation panel (FR-LU08) and the parameter unit (FR-PU07) can be performed.
Decreasing the setting value lowers the contrast.
Pr.
Name
991
PU contrast adjustment
E105
The above parameter is displayed as a simple mode parameter only when the LCD operation panel (FR-LU08) and the
parameter unit (FR-PU07) are connected.
page 242
page 204
page 214
Initial value
Initial value
1
Initial value
58
Setting range
0
Japanese
1
English
2
German
3
French
4
Spanish
5
Italian
6
Swedish
7
Finnish
Setting range
0
Turns the key sound and buzzer OFF.
1
Turns the key sound and buzzer ON.
Setting range
0: Low  63: High
0 to 63
5.4 (E) Environment setting parameters
Description
Description
Description
165
5. PARAMETERS
3
4
5
5
5
6
7
8
9
10