5.7.1
Motor overheat protection (electronic thermal O/L relay)
Set the current of the electronic thermal O/L relay function to protect the motor from overheating. Such settings will provide the
optimum protective characteristic considering the low cooling capability of the motor during low-speed operation.
Pr.
9
Electronic thermal O/L relay
H000
600
First free thermal reduction
H001
frequency 1
601
First free thermal reduction
H002
ratio 1
602
First free thermal reduction
H003
frequency 2
603
First free thermal reduction
H004
ratio 2
604
First free thermal reduction
H005
frequency 3
607
Motor permissible load level
H006
51
Second electronic thermal O/L
H010
relay
692
Second free thermal reduction
H011
frequency 1
693
Second free thermal reduction
H012
ratio 1
694
Second free thermal reduction
H013
frequency 2
695
Second free thermal reduction
H014
ratio 2
696
Second free thermal reduction
H015
frequency 3
608
Second motor permissible load
H016
level
561
PTC thermistor protection level
H020
1016
PTC thermistor protection
H021
detection time
*1
The setting range for FR-F860-00680 or lower. The minimum setting increment is "0.01 A".
*2
The setting range for FR-F860-01080 or higher. The minimum setting increment is "0.1 A".
230
5. PARAMETERS
5.7 (H) Protective function parameter
Name
Initial value
Inverter
rated current
9999
100%
9999
100%
9999
150%
9999
9999
100%
9999
100%
9999
9999
9999
0 s
Setting range
*1
Set the rated motor current.
0 to 500 A
*2
0 to 3600 A
0 to 590 Hz
The electronic thermal O/L relay operation level can be
changed to match the motor temperature characteristics
9999
with the combination of these three points (Pr.600,
1 to 100%
Pr.601), (Pr.602, Pr.603), (Pr.604, Pr.9).
9999
9999: Free thermal O/L relay invalid
0 to 590 Hz
9999
1 to 100%
9999
0 to 590 Hz
9999
110 to 250%
Set the permissible load according to the motor
characteristics.
Enabled when the RT signal is ON.
*1
0 to 500 A
Set the rated motor current.
*2
0 to 3600 A
9999
Second electronic thermal O/L relay invalid
0 to 590 Hz
The electronic thermal O/L relay operation level can be
changed to match the second motor temperature
9999
characteristics with the combination of these three points
1 to 100%
(Pr.692, Pr.693), (Pr.694, Pr.695), (Pr.696, Pr.51).
9999
9999: Second free thermal O/L relay invalid
0 to 590 Hz
9999
1 to 100%
9999
0 to 590 Hz
9999
110 to 250%
Set the permissible load when the RT signal is ON.
9999
The Pr.607 setting is applied even when the RT signal is
ON.
0.5 to 30 kΩ
Set the PTC thermistor protection level (resistance).
9999
PTC thermistor protection disabled
0 to 60 s
Set the time from when the resistance of the PTC
thermistor reaches the protection level until the protective
function is activated.
Description