5.6.2
Startup in Network operation mode at power-ON
When power is switched ON or when power comes back ON after an instantaneous power failure, the inverter can be started
up in the Network operation mode. After the inverter starts up in the Network operation mode, parameter writing and operation
can be commanded from programs.
Set this mode when performing communication operation using the RS-485 terminals or a communication option.
Pr.
Name
79
Operation mode selection
D000
340
Communication startup mode
D001
selection
 Selecting the operation mode for power-ON (Pr.340)
• Depending on the Pr.79 and Pr.340 settings, the operation mode at power-ON (reset) changes as described below.
Pr.340
Pr.79
Operation mode at power-ON, at power restoration,
setting
setting
0
0 (initial
External operation mode
(initial
value)
value)
1
PU operation mode
2
External operation mode
3, 4
External/PU combined operation mode
6
External operation mode
7
X12 (MRS) signal ON External operation mode
X12 (MRS) signal OFF External operation mode
0
NET operation mode
*1
1, 2
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
7
X12 (MRS) signal ON NET operation mode
X12 (MRS) signal OFF External operation mode
0
NET operation mode
*1
10, 12
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
7
External operation mode
*1
Use Pr.340="2 or 12" setting to perform communication with the RS-485 terminals. Even if an instantaneous power failure occurs while Pr.57
Restart coasting time ≠ "9999" (with automatic restart after instantaneous power failure), inverter continues operation at the condition before
the instantaneous failure.
*2
The operation mode cannot be directly changed between the PU operation mode and Network operation mode.
*3
Switching between the PU and NET operation modes is available with the
Initial
Setting
value
range
0
0 to 4, 6, 7
Selects the operation mode.
(Refer to
0
0
Follows the Pr.79 setting.
1, 2
The inverter starts up in the Network operation mode.
If an instantaneous power failure occurs when "2" is set, the
operating status before the instantaneous power failure is
maintained.
10, 12
The inverter starts up in the Network operation mode. The
operation mode can be changed between the PU operation mode
and Network operation mode from the operation panel.
If an instantaneous power failure occurs when "12" is set, running
is continued at the condition before the instantaneous power
failure.
or after a reset
Description
page
204.)
Operation mode switching
Switching among the External, PU, and NET operation
*2
modes is enabled.
PU operation mode fixed
Switching between the External and NET operation modes
is enabled.
Switching to PU operation mode is disabled
Operation mode switching is disabled
Switching among the External, PU, and NET operation
mode is enabled while running.
Switching among the External, PU, and NET operation
*2
modes is enabled.
External operation mode fixed. (Forcibly switched to
External operation mode.)
Same as Pr.340="0" setting
Switching between the PU and NET operation mode is
*3
enabled
Same as Pr.340="0" setting
NET operation mode fixed
Same as Pr.340="0" setting
Switching between the PU and NET operation mode is
*3
enabled while running.
Same as Pr.340="0" setting
key on the operation panel or the X65 signal.
5.6 (D) Operation command and frequency command
3
4
5
5
5
6
7
8
9
10
213
5. PARAMETERS