 Input/output signals
• Assigning the PID control valid terminal signal (X14) to the input terminal by Pr.178 to Pr.189 (Input terminal function
selection) enables PID control to be performed only when the X14 signal is turned ON. When the X14 signal is OFF,
regular inverter running is performed without PID action. (When the X14 signal is not assigned, PID control is enabled only
by setting Pr.128 ≠ "0".)
• Input signal
Signal
Function
X14
PID control valid terminal
X80
Second PID control valid
terminal
PDI1
PID multistage set point
setting 1
PDI2
PID multistage set point
setting 2
PDI3
PID multistage set point
setting 3
X64
During retry
X79
Second PID forward/
reverse action switchover
X72
PID P control switchover
X73
Second PID P control
switchover
• Output signal
Signal
Function
FUP
PID upper limit
FUP2
Second PID upper limit
FDN
PID lower limit
FDN2
Second PID lower limit
RL
PID forward/reverse
rotation output
RL2
Second PID forward/
reverse rotation output
PID
During PID control
activated
PID2
Second During PID
control activated
Y48
PID deviation limit
Y205
Second PID deviation limit 205
SLEEP
PID output interruption
SLEEP2
During second PID output
shutoff
NOTE
• Changing the terminal functions with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters
after confirming the function of each terminal.
Pr.178 to Pr.189
setting
14
When the signal is assigned to the input terminal, PID control is enabled
when the signal is ON.
80
38
The set point set in Pr.1460 to Pr.1466 can be selected by combining the
ON/OFF status of the signals.
39
40
64
PID control is switched between forward and reverse action without
changing parameters by turning ON the signal.
79
72
Integral and differential values can be reset by turning the signal ON.
73
Pr.190 to Pr.196
setting value
positive
negative
logic
logic
15
115
Output when the measured value signal exceeds Pr.131 PID upper limit
(Pr.1143 Second PID upper limit).
201
301
14
114
Output when the measured value signal falls below Pr.132 PID lower limit
(Pr.1144 Second PID lower limit).
200
300
16
116
"Hi" is output when the output display of the parameter unit is forward
rotation (FWD), and "Low" is output when the display is reverse rotation
(REV) and stop (STOP).
202
302
47
147
Turns ON during PID control.
When the PID calculation result is reflected to the output frequency (Pr.128
< "2000"), the PID signal turns OFF at turn OFF of the start signal.
203
303
When the PID calculation result is not reflected to the output frequency
(Pr.128  "2000"), the PID signal turns ON during PID calculation
regardless of the start signal status.
48
148
Output when the absolute deviation value exceeds the limit value set in
Pr.553 PID deviation limit (Pr.1145 Second PID deviation limit).
305
70
170
Set Pr.575 Output interruption detection time (Pr.1147 Second output
interruption detection time)  "9999". This signal turns ON when the PID
204
304
output suspension function is activated.
Description
Description
5. PARAMETERS
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10