Mitsubishi Electric 800 Series Instruction Manual page 339

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.9.7
Checking of current input on analog input terminal
When current is input to the analog input terminal 2 and terminal 4, operation when the current input has gone below the
specified level (loss of analog current input) can be selected. It is possible to continue the operation even when the analog
current input is lost.
Pr.
573
4 mA input check selection
T052
777
4 mA input check operation
T053
frequency
A681
778
4 mA input check filter
T054
A682
338
5. PARAMETERS
5.9 (T) Multi-Function Input Terminal Parameters
Name
Initial
value
9999
9999
0 s
Setting
range
1
Operation continues with output frequency
before the current input loss.
2
4 mA input fault (E.LCI) is activated when the
current input loss is detected.
3
The inverter output decelerates the motor to a
stop when the current input loss is detected.
After the motor is stopped, 4 mA input fault
(E.LCI) is activated.
4
Operation continues at the frequency set in
Pr.777.
11
Operation continues at the output frequency
before the current input loss.
12
4 mA input fault (E.LCI) is activated when the
current input loss is detected.
13
The inverter output decelerates the motor to a
stop when the current input loss is detected.
After the motor is stopped, 4 mA input fault
(E.LCI) is activated.
14
Operation continues at the frequency set in
Pr.777.
21
Operation continues at the output frequency
before the current input loss.
22
4 mA input fault (E.LCI) is activated when the
current input loss is detected.
23
The inverter output decelerates the motor to a
stop when the current input loss is detected.
After the motor is stopped, 4 mA input fault
(E.LCI) is activated.
24
Operation continues at the frequency set in
Pr.777.
9999
No current input check
0 to 590 Hz
Set the frequency to continue operation when the current input is lost.
(Valid when Pr.573 = "4, 14, or 24")
9999
No current input check when Pr.573 = "4, 14, or 24"
0 to 10 s
Set the current input loss detection time.
Description
Check the current
input on terminals 2
and 4.
Check the current
input on terminal 4.
Check the current
input on terminal 2.

Advertisement