Mitsubishi Electric 800 Series Instruction Manual page 202

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.5.4
Starting frequency and start-time hold function
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
It is possible to set the starting frequency and hold the set starting frequency for a certain period of time.
Set these functions when a starting torque is needed or the motor drive at start needs smoothing.
Pr.
Name
13
Starting frequency
F102
571
Holding time at a start
F103
 Starting frequency setting (Pr.13)
• The frequency at start can be set in the range of 0 to 60 Hz.
• Set the starting frequency at which the start signal is turned ON.
Output
frequency
(Hz)
60
Pr.13
0
STF
ON
NOTE
• The inverter does not start if the frequency setting signal is less than the value set in Pr.13. For example, while Pr.13 = 5
Hz, the inverter output starts when the frequency setting signal reaches 5 Hz.
 Start-time hold function (Pr.571)
• This function holds during the period set in Pr.571 and the output frequency set in Pr.13 Starting frequency.
• This function performs initial excitation to smooth the motor drive at a start.
Output
frequency
(Hz)
60
Pr.13
0
Pr. 571 setting time
STF
ON
NOTE
• When Pr.13 ="0 Hz", the starting frequency is held at 0.01 Hz.
• When the start signal was turned OFF during start-time hold, deceleration is started at that point.
• At switching between forward rotation and reverse rotation, the starting frequency is valid but the start-time hold function
is invalid.
CAUTION
• Note that when Pr.13 is set to any value equal to or lower than the setting of Pr.2 Minimum frequency, simply turning ON the start signal
will run the motor at the frequency set in Pr.2 even if the command frequency is not input.
Parameters referred to
page 253
Pr.2 Minimum frequency
Initial value
0.5 Hz
9999
Time
Time
5.5 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Setting range
0 to 60 Hz
Set the starting frequency at which the
start signal is turned ON.
0 to 10 s
Set the holding time of Pr.13.
9999
The holding function at a start is invalid.
Description
10
201
5. PARAMETERS
3
4
5
5
5
6
7
8
9

Advertisement

Table of Contents
loading

Table of Contents