2.6

Control circuit

2.6.1
Details on the control circuit terminals
 Input signal
Type
Terminal
Common
symbol
*1
SD (sink
STF
(negative
common))
PC
*1
STR
(source
(positive
common))
STP
*1
(STOP)
RH, RM,
*1
RL
*1
JOG
*1
RT
*1
MRS
*1
RES
*1
AU
*1
CS
50
2. INSTALLATION AND WIRING
2.6 Control circuit
Terminal name
Forward rotation
Turn ON the STF signal to start
start
forward rotation and turn it OFF to
stop.
Reverse rotation
Turn ON the STR signal to start
start
reverse rotation and turn it OFF to
stop.
Start self-holding
Turn ON the STP (STOP) signal to self-hold the start
selection
signal.
Multi-speed
Multi-speed can be selected according to the
selection
combination of RH, RM and RL signals.
Jog mode
Turn ON the JOG signal to enable JOG operation (initial
selection
setting) and turn ON the start signal (STF or STR) to
start JOG operation.
Pulse train input
Terminal JOG is also used as a pulse train input
terminal. To use as a pulse train input terminal, change
the Pr.291 setting. (maximum input pulse: 100k pulses/
s)
Second function
Turn ON the RT signal to enable the second function.
selection
When the second function such as "second torque
boost" and "second V/F (base frequency)" is set,
turning ON the RT signal enables the selected function.
Output stop
Turn ON the MRS signal (2 ms or more) to stop the
inverter output.
Use this signal to shut off the inverter output when
stopping the motor with an electromagnetic brake.
Reset
Use this signal to reset a fault output provided when a
protective function is activated. Turn ON the RES signal
for 0.1 s or longer, then turn it OFF.
In the initial setting, reset is set always-enabled. By
setting Pr.75, reset can be set enabled only at fault
occurrence. The inverter recovers about 1 s after the
reset is released.
Terminal 4 input
The terminal 4 function is available only when the AU
selection
signal is turned ON.
Turning the AU signal ON makes terminal 2 invalid.
No function
Use Pr.186 CS terminal function selection for
function assignment.
Terminal function description
When the STF
and STR signals
are turned ON
simultaneously,
the stop
command is
given.
Rated
Refer
specification
to
page
Input resistance
550
4.7 k
Voltage when
contacts are open:
21 to 27 VDC
When contacts are
short-circuited:
4 to 6 mADC
550
226
224
Input resistance
222
2 k
When contacts are
short-circuited:
8 to 13 mADC
Input resistance
348
4.7 k
Voltage when
contacts are open:
21 to 27 VDC
346
When contacts are
short-circuited:
4 to 6 mADC