5.13.8
Output stop function
The motor coasts to a stop (inverter output shutoff) when inverter output frequency falls to Pr. 522 setting or lower.
Pr.
522
Output stop frequency
G105
• When both of the frequency setting signal and output frequency falls to the frequency set in Pr. 522 or lower, the inverter
stops the output and the motor coasts to a stop.
• At a stop condition, the motor starts running when the frequency setting signal exceeds Pr.522 + 2 Hz. The motor is
accelerated at the Pr.13 Starting frequency (0.01 Hz under PM motor control) at the start.
*1
The output frequency before the slip compensation is compared with the Pr.522 setting.
*1
At a stop condition, the motor is accelerated at the Pr.13 Starting frequency (0.01 Hz under PM motor control).
*2
The output frequency to be compared with the Pr.522 setting is the output frequency before slip compensation (V/F control and Advanced
magnetic flux vector control), or the speed command value converted into the frequency (PM motor control).
*3
Steepness of the slope depends on the acceleration/deceleration time settings such as Pr.7.
548
5. PARAMETERS
5.13 (G) Control parameters
Name
Initial value
9999
Example of when target frequency>Pr.522+2 Hz, and start signal is ON/OFF
Output frequency
∗1
Target frequency
(fixed)
Pr.522+2 Hz
Pr.522
Pr.13
STF
RUN
Example of: target frequency = analog input command, start signal always ON
Analog input command
Pr.522+2 Hz
Pr.522
∗2
Output frequency
∗3
Pr.522+2 Hz
Pr.522
∗1
Pr.13
Inverter output
shutoff
STF
RUN
Setting
range
0 to 590 Hz
Set the frequency to start coasting to a stop (output shutoff).
9999
No function
Inverter output shutoff