Mitsubishi Electric 800 Series Instruction Manual page 432

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

NOTE
• The motor 1 (M1) starts first when power is turned ON for the first time or after inverter reset.
• When the Pr.578 or Pr.579 setting has been changed, The motor 1 (M1) starts first.
 Connection diagram
• Basic system
(Pr.579 = "0")
-
Sink logic
-
Pr.183=14
-
Pr.185=64
-
Pr.194=72
-
Pr.193=73
-
Pr.194=74
Power
supply
Forward rotation
Reverse rotation
PID control
selection
PID forward/
reverse action
switchover
Setting
potentiometer
(Set point setting)
*1
Prepare the power supply in accordance with the power supply specifications of the detector.
*2
The applied output signal terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
*3
The applied input signal terminals differ by the settings of Pr.178 to Pr.189 (Input terminal function selection).
*4
There is no need to input AU signal.
MC
RO4
RO3
Inverter
RO2
RST
UVW
STF
STR
RT(X14)
*3
JOG(X64)
*3
SD
MC RO2
∗2
(RO2)FU
10
MC RO3
2
∗2
(RO3)OL
5
MC RO4
∗2
(RO4)IPF
1
SE
4
*4
(Measured value) 4 to 20 mA
0
24 V
∗1
Power supply
Distributed water
M4
Pump 4
M3
Pump 3
M2
Pump 2
M1
Pump 1
Supplied water
For 2-wire type Detector
-
24 VDC
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10
+
431