 Input compensation of multi-speed setting (Pr.28)
• Speed (frequency) compensation can be applied for the multi-speed setting and the remote setting by inputting the
frequency setting compensation signal (terminals 1, 2).
NOTE
• The priority of the frequency commands by the external signals are "Jog operation > multi-speed operation > terminal 4
analog input > pulse train input > terminal 2 analog input". (For details on frequency commands by analog input, refer to
page
328.)
• Valid in the External operation mode or PU/External combined operation mode (Pr.79= "3" or "4").
• Multi-speed parameters can also be set during PU operation or External operation.
• The Pr.24 to Pr.27 and Pr.232 to Pr.239 settings have no priority among them.
• When Pr.59 Remote function selection ≠ "0", the multi-speed setting is invalid since the RH, RM, and RL signals are for
remote setting.
• When performing analog input compensation, set Pr.28 Multi-speed input compensation selection to "1".
• Select the terminals (terminals 1, 2) to use for compensation input voltage (0 to ± 5 V, 0 to ± 10 V) at Pr.73 Analog input
selection.
• When using terminal 1 for compensation input, set Pr.868 Terminal 1 function assignment "0" (initial value).
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.15 Jog frequency
Pr.59 Remote function selection
Pr.73 Analog input selection
Pr.79 Operation mode selection
Pr.178 to Pr.189 (Input terminal function selection)
Pr.868 Terminal 1 function assignment
228
5. PARAMETERS
5.6 (D) Operation command and frequency command
page 224
page 197
page 318
page 204
page 322
page 343