 Output signal list
• The functions of the output terminals can be set.
• Refer to the following table and set each parameter. (0 to 99, 200 to 299: Positive logic, 100 to 199, 300 to 399: Negative
logic)
Setting
Positive
Negative
logic
logic
0
100
1
101
2
102
3
103
4
104
5
105
7
107
8
108
10
110
11
111
12
112
13
113
14
114
15
115
16
116
17
18
19
23
123
25
125
126
26
35
135
39
139
40
140
41
141
42
142
298
5. PARAMETERS
5.8 (M) Monitor display and monitor output signal
Signal
Function
name
RUN
Inverter running
SU
*1
Up to frequency
IPF
Instantaneous power
*2
failure/undervoltage
OL
Overload warning
FU
Output frequency detection
FU2
Second output frequency
detection
For manufacturer setting. Do not set.
THP
Electronic thermal O/L relay
pre-alarm
PU
PU operation mode
RY
Inverter operation ready
Y12
Output current detection
Y13
Zero current detection
FDN
PID lower limit
FUP
PID upper limit
RL
PID forward/reverse rotation
output
MC1
Electronic bypass MC1
MC2
Electronic bypass MC2
MC3
Electronic bypass MC3
ALM4
Output short-circuit
detection
FAN
Fan fault output
FIN
Heat sink overheat pre-
alarm
TU
Torque detection
Y39
Start time tuning completion Output when tuning is completed during start-
Y40
Trace status
FB
Speed detection
FB2
Second speed detection
Operation
Output during operation when the inverter
output frequency reaches Pr.13 Starting
frequency or higher.
Output when the output frequency reaches the
set frequency.
Output when an instantaneous power failure or
undervoltage protection operation occurs.
Output during operation of the stall prevention
function.
Output when the output frequency reaches the
frequency set in Pr.42 (Pr.43 during reverse
rotation) or higher.
Output when the output frequency reaches the
frequency set in Pr.50 or higher.
Output when the cumulative electronic thermal
O/L relay value reaches 85% of the trip level.
(Electronic thermal O/L relay protection (E.THT/
E.THM) is activated when the value reaches
100%.)
Output when PU operation mode is selected.
Output when the reset process is completed
after powering ON the inverter (when starting is
possible by switching the start signal ON or
during operation).
Output when the output current is higher than
the Pr.150 setting for the time set in Pr.151 or
longer.
Output when the output current is lower than the
Pr.152 setting for the time set in Pr.153 or
longer.
Output when the value is lower than the lower
limit of PID control.
Output when the value is higher than the upper
limit of PID control.
Output during forward rotation under PID
control.
Used when using the electronic bypass
function.
Output when E.SCF occurs or when E.GF
occurs while Pr.249 = "2".
Output when a fan fault occurs.
Output when the heat sink temperature reaches
about 85% of the heat sink overheat protection
operation temperature.
Output when the motor torque is higher than the
Pr.864 setting.
up.
Output during trace operation.
Output when the actual motor rotations per
minute (estimated rotations per minute) reaches
Pr.42 (Pr.50).
Related
Refer
parameter
to
page
303
Pr.41
305
Pr.57
448,
454
Pr.22, Pr.23,
257
Pr.66, Pr.148,
Pr.149, Pr.154
Pr.42, Pr.43
305
Pr.50
305
Pr.9
230
Pr.79
204
303
Pr.150, Pr.151
307
Pr.152, Pr.153
307
Pr.127 to Pr.134,
396
Pr.575 to Pr.577,
Pr.1346, Pr.1370
Pr.135 to Pr.139,
376
Pr.159
Pr.521, Pr.249
238,
240
Pr.244
237
578
Pr.864
309
Pr.95, Pr.574
371
Pr.1020 to
396
Pr.1047
Pr.42, Pr.50
305