Mitsubishi Electric 800 Series Instruction Manual page 64

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.6.6
When supplying 24 V external power to the control circuit
Connect the 24 V external power supply across terminals +24 and SD to turn the I/O terminal ON/OFF operation, keep the
operation panel ON, and carry out communication with other devices even at power-OFF state of inverter's main circuit power
supply. When the main circuit power supply is turned ON, the power supply source changes from the 24 V external power
supply to the main circuit power supply.
 Specification of the applicable 24 V external power supply
Item
Input voltage
23 to 25.5 VDC
Input current
1.4 A or less
Commercially available products (as of October 2020)
Model
Specifications: Capacity 50 W, output voltage 24 VDC, output
*1
S8FS-G05024C
current 2.2 A
Installation method: Direct installation, screw type terminal block
with cover
Input: Single-phase 100 to 240 VAC
Specifications: Capacity 60 W, output voltage 24 VDC, output
*1
S8VK-S06024
current 2.5 A
Installation method: DIN rail, push-in (spring) type terminal block
Input: Single-phase 100 to 240 VAC
Specifications: Capacity 240 W, output voltage 24 VDC, output
*1
S8VK-WA24024
current 10 A
Installation method: DIN rail, push-in (spring) type terminal block
Input: Three-phase 200 to 240 VAC
*1
For the latest information about OMRON power supply, contact OMRON corporation.
 Starting and stopping the 24 V external power supply operation
• Supplying 24 V external power while the main circuit power is OFF starts the 24 V external power supply operation.
Likewise, turning OFF the main circuit power while supplying 24 V external power starts the 24 V external power supply
operation.
• Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation.
NOTE
• During the 24 V external power supply operation, the inverter operation is disabled.
• In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is
performed in the inverter, then the power supply changes to the main circuit power supply. (The reset can be disabled using
Pr.30. (Refer to
page
553.))
 Confirming the 24 V external power supply input
• During the 24 V external power supply operation, the alarm lamp flickers.
• During the 24 V external power supply operation, the 24 V external power supply operation signal (EV) is output. To use
the EV signal, set "68 (positive logic) or 168 (negative logic)" in one of Pr.190 to Pr.196 (Output terminal function
selection) to assign function to an output terminal.
Rated specification
Product overview
POWER ALARM
OMRON Corporation
Flickering
Manufacturer
2. INSTALLATION AND WIRING
2.6 Control circuit
3
2
3
4
5
6
7
8
9
10
63