 Arrangement of multiple inverters
When multiple inverters are placed in the same enclosure, generally arrange them horizontally as shown in the right figure (a).
When it is inevitable to arrange them vertically to minimize space, take such measures as to provide guides since heat from
the bottom inverters can increase the temperatures in the top inverters, causing inverter failures.
When mounting multiple inverters, fully take caution not to make the surrounding air temperature of the inverter higher than the
permissible value by providing ventilation and increasing the enclosure size.
• Arrangement of multiple inverters
Inverter
Inverter
Enclosure
(a) Horizontal arrangement
 Arrangement of the ventilation fan and inverter
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling fan. When installing a
ventilation fan for that heat, determine the place of ventilation fan installation after fully considering an air flow. (Air passes
through areas of low resistance. Make an airway and airflow plates to expose the inverter to cool air.)
• Arrangement of the ventilation fan and inverter
Inverter
<Good example>
36
2. INSTALLATION AND WIRING
2.3 Installation of the inverter and enclosure design
Inverter
Inverter
Guide
Guide
Guide
Inverter
Inverter
Enclosure
(b) Vertical arrangement
Inverter
<Bad example>