5.9.1
Analog input selection
The functions to switch the analog input terminal specifications, override function, forward/reverse rotation by the input signal
polarity are selectable.
Pr.
Name
73
Analog input selection 1
T000
267
Terminal 4 input
T001
selection
 Analog input specification selection
• Concerning the terminals 2 and 4 used for analog input, the voltage input (0 to 5 V, 0 to 10 V) and current input (0 to 20
mA) are selectable. To change the input specification, change the parameters (Pr.73, Pr.267) and voltage/current input
switch settings (switches 1, 2).
Voltage/current
input switch
Switch 2
Switch 1
2
4
Switch state
Switch 1
ON
OFF
Switch 2
ON
OFF
• Change the setting of the voltage/current input selection switch to change the rated specification of terminal 2 or 4.
• Correctly set Pr.73, Pr.267 and voltage/current input switch settings so that the analog signal appropriate for the settings
is input. The incorrect settings shown in the table below cause a failure. Other incorrect settings result in an incorrect
operation.
Setting causing a failure
Switch setting
ON (current input)
OFF (voltage input)
318
5. PARAMETERS
5.9 (T) Multi-Function Input Terminal Parameters
Initial value
0
Input specification
Current input
Voltage input (initial status)
Current input (initial status)
Voltage input
Terminal input
Voltage input
Causes an analog signal output circuit failure in an external device
(due to increased loads on the signal output circuit of the external device).
Current input
Causes an input circuit failure in the inverter
(due to an increased output power in the analog signal output circuit of an external device).
Setting range
0 to 5, 10 to 15
Switch 1 - OFF
(initial status)
6, 7, 16, 17
Switch 1 - ON
0
Switch 2 - ON
(initial status)
1
Switch 2 - OFF
2
Input
terminal
Terminal 2
For voltage input, the input resistance is 10±1 kΩ and the maximum
permissible voltage is 20 VDC.
For current input, the input resistance is 245±5 Ω and the maximum
Terminal 4
permissible current is 30 mA.
Description
The terminal 2 input specification (0 to 5
V, 0 to 10 V, 0 to 20 mA) and terminal 1
input specification (0 to ±5 V, 0 to ±10 V)
are selectable.
Also the override and reversible
operation settings are selectable.
Terminal 4 input, 4 to 20 mA
Terminal 4 input, 0 to 5 V
Terminal 4 input, 0 to 10 V
Rated specification
Operation