Injury Prevention
CAUTION
The voltage applied to each terminal must be the ones specified in the Instruction Manual. Otherwise
an explosion or damage may occur.
The cables must be connected to the correct terminals. Otherwise an explosion or damage may
occur.
The polarity (+ and -) must be correct. Otherwise an explosion or damage may occur.
While power is ON or for some time after power-OFF, do not touch the inverter as it will be extremely
hot. Touching these devices may cause a burn.
Additional Instructions
The following instructions must be also followed. If the product is handled incorrectly, it may cause unexpected fault, an injury,
or an electric shock.
CAUTION
Transportation and installation
Any person who is opening a package using a sharp object, such as a knife and cutter, must wear
gloves to prevent injuries caused by the edge of the sharp object.
The product must be transported in correct method that corresponds to the weight. Failure to do so
may lead to injuries.
Do not stand or rest heavy objects on the product.
Do not stack the boxes containing inverters higher than the number recommended.
When carrying the inverter, do not hold it by the front cover; it may fall off or fail.
During installation, caution must be taken not to drop the inverter as doing so may cause injuries.
The product must be installed on the surface that withstands the weight of the inverter.
Do not install the product on a hot surface.
The mounting orientation of the inverter must be correct.
The inverter must be installed on a strong surface securely with screws so that it will not drop.
Do not install or operate the inverter if it is damaged or has parts missing.
Foreign conductive objects must be prevented from entering the inverter. That includes screws and
metal fragments or other flammable substance such as oil.
As the inverter is a precision instrument, do not drop or subject it to impact.
For the FR-F860-00090 or lower, the surrounding air temperature must be -10 to +30°C for the SLD
rating (-10 to +40°C for the LD rating) (non-freezing). Otherwise the inverter may be damaged.
For the FR-F860-00170 to 01080, the surrounding air temperature must be -10 to +40°C (non-
freezing). Otherwise the inverter may be damaged.
For the FR-F860-01440 or higher, the surrounding air temperature must be -10 to +40°C for the SLD
rating (-10 to +50°C for the LD rating) (non-freezing). Otherwise the inverter may be damaged.
The ambient humidity must be 95%RH or less (non-condensing). Otherwise the inverter may be
damaged. (Refer to
page 31
for details.)
3