 Cleaning operation by the cleaning signal (X97 signal)
• When the X97 signal is assigned to an input terminal, the cleaning operation can be finished when the cleaning signal (X97)
is turned from ON to OFF.
• For the X97 signal input, set "97" in any of Pr.178 to Pr.189 to assign the function.
Pr.1470
X97 signal
setting
Assignment
0
Optional
Other
Not assigned
than 0
Assigned
NOTE
• When a trigger occurs during the following operations, the cleaning operation is started upon completion of the following
operations. Automatic restart after instantaneous power failure, online auto tuning at startup
• The following functions are disabled during cleaning operation. PID control automatic switchover frequency, PID control
sleep function, pre-charge fault, determination of pre-charge ending with parameters, PID gain tuning, electronic bypass
with the automatic switchover frequency of the inverter (Pr.139), automatic switchover of auxiliary motors of the multi-pump
function, output stop function (Pr.522), restart at every start during cleaning
• When the stall prevention is activated during acceleration of the cleaning function, the operation is shifted to the cleaning
deceleration operation.
• If the number of cleaning times set in Pr.1470 is an even number, the operation is shifted to the normal operation after the
cleaning forward/reverse operation time (Pr.1473/Pr.1475) of the final cleaning operation has elapsed.
• Changing the terminal assignment with Pr.178 to Pr.189 and Pr.190 to Pr.196 may affect other functions. Set parameters
after confirming the function of each terminal.
Parameters referred to
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
Pr.7 Acceleration time, Pr.8 Deceleration time
Cleaning
operation
ON/OFF
Optional
Invalid
-
Enabled
OFF
Invalid
ON
Enabled
page 343
page 297
page 190
Cleaning end condition
-
After cleaning is performed for the number of times set in Pr.1470
-
• After cleaning is performed for the number of times set in Pr.1470
• When X97 signal turns OFF
5. PARAMETERS
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10
395