5.9.5
Frequency setting voltage (current) bias and gain
The degree (incline) of the output frequency to the frequency setting signal (0 to 5 VDC, 0 to 10 V or 4 to 20 mA) is selectable
to a desired amount.
Use Pr.73 Analog input selection, Pr.267 Terminal 4 input selection, or the voltage/current input switch to switch among
input 0 to 5 VDC, 0 to 10 V, and 4 to 20 mA. (Refer to
Pr.
902
Terminal 2 frequency setting bias
T200
frequency
902
Terminal 2 frequency setting bias
T201
125
903
Terminal 2 frequency setting gain
T022
T202
frequency
903
Terminal 2 frequency setting gain
T203
904
Terminal 4 frequency setting bias
T400
frequency
904
Terminal 4 frequency setting bias
T401
126
905
Terminal 4 frequency setting gain
T042
T402
frequency
905
Terminal 4 frequency setting gain
T403
917
Terminal 1 bias frequency (speed)
T100
917
Terminal 1 bias (speed)
T101
918
Terminal 1 gain frequency (speed)
T102
918
Terminal 1 gain (speed)
T103
241
Analog input display unit
M043
switchover
328
5. PARAMETERS
5.9 (T) Multi-Function Input Terminal Parameters
page
Name
Initial value
0 Hz
0%
60 Hz
100%
0 Hz
20%
60 Hz
100%
0 Hz
0%
60 Hz
100%
0
318)
Setting
range
0 to 590 Hz
Set the terminal 2 input bias side frequency.
0 to 300%
Set the converted % on the bias side voltage
(current) of the terminal 2 input.
0 to 590 Hz
Set the terminal 2 input gain (maximum)
frequency.
0 to 300%
Set the converted % on the gain side voltage
(current) of the terminal 2 input.
0 to 590 Hz
Set the terminal 4 input bias side frequency.
0 to 300%
Set the converted % on the bias side current
(voltage) of terminal 4 input.
0 to 590 Hz
Set the terminal 4 input gain (maximum)
frequency.
0 to 300%
Set the converted % on gain side current (voltage)
of terminal 4 input.
0 to 590 Hz
Set the terminal 1 input bias side frequency
(speed). (speed limit)
0 to 300%
Set the converted % on bias side voltage of
terminal 1 input. (speed limit)
0 to 590 Hz
Set the terminal 1 input gain (maximum)
frequency (speed). (speed limit)
0 to 300%
Set the converted % on the gain side voltage of
terminal 1 input. (speed limit)
0
% display
1
V/mA display
Description
Select the unit for analog input
display