Pr.
Name
453
Second motor capacity
C201
454
Number of second
C202
motor poles
51
Second electronic
C203
thermal O/L relay
456
Rated second motor
C204
voltage
457
Rated second motor
C205
frequency
744
Second motor inertia
C207
(integer)
745
Second motor inertia
C208
(exponent)
463
Second motor auto
C210
tuning setting/status
458
Second motor constant
C220
(R1)
459
Second motor constant
C221
(R2)
460
Second motor constant
C222
(L1) / d-axis inductance
(Ld)
461
Second motor constant
C223
(L2) / q-axis inductance
(Lq)
462
Second motor constant
C224
(X)
455
Second motor
C225
excitation current
860
Second motor torque
C226
current/Rated PM motor
current
560
Second frequency
A712
search gain
*1
For the FR-F860-00680 or lower.
*2
For the FR-F860-01080 or higher.
*3
The setting range and unit change according to the Pr.71 (Pr.450) setting.
354
5. PARAMETERS
5.10 (C) Motor constant parameters
Initial value
Setting range
9999
*1
0.4 to 55 kW
*2
0 to 3600 kW
9999
9999
2, 4, 6, 8, 10, 12
9999
9999
*1
0 to 500 A
*2
0 to 3600 A
9999
575 V
0 to 1000 V
9999
10 to 400 Hz
9999
9999
10 to 999, 9999
9999
10 to 7, 9999
0
0
1
11
101
9999
*1 *3
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
9999
*1 *3
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
9999
0 to 6000 mH, 9999
0 to 400 mH, 9999
9999
0 to 6000 mH, 9999
0 to 400 mH, 9999
9999
0 to 100%, 9999
9999
0 to 500 A, 9999
0 to 3600 A, 9999
9999
0 to 500 A, 9999
0 to 3600 A, 9999
9999
0 to 32767
9999
Set the capacity of the second motor.
V/F control
Set the number of poles of the second motor.
V/F control
This function is enabled when the RT signal is
ON.
Set the rated motor current.
Second electronic thermal O/L relay disabled
Set the rated voltage (V) of the second motor.
Set the rated frequency (Hz) of the second motor.
Use the Pr.84 Rated motor frequency setting.
Set the inertia of the second motor.
9999: Uses the constant value of standard motor.
No auto tuning for the second motor.
Performs offline auto tuning without rotating the
second motor.
Performs offline auto tuning without rotating the
motor (V/F control) (Refer to
Performs offline auto tuning by rotating the
second motor.
Tuning data of the second motor
(The value measured by offline auto tuning is
*2 *3
automatically set.)
9999: Uses the constant value of standard motor.
*2 *3
*1 *3
*2 *3
*1 *3
*2 *3
*3
*1 *3
*2 *3
*1 *3
*2 *3
The offline auto tuning automatically sets the gain
required for the frequency search of the second
motor.
Uses the constant value of standard motor.
Description
page
363)